72<br />

Performance<br />

Data<br />

(10 Ton)<br />

High Efficiency<br />

Table PD-84 — Belt Drive Evaporator Fan Performance — 10-Ton — YHC120A3,A4,AW *L,M — Low and Medium Heat — Horizontal Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

3-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

3200 — — 777 1.15 814 1.28 853 1.42 895 1.59 936 1.76 973 1.93 1008 2.09 1037 2.24 1064 2.38<br />

3600 819 1.42 857 1.57 890 1.71 922 1.85 957 2.02 994 2.20 1032 2.39 1067 2.58 1099 2.77 1131 2.96<br />

4000 902 1.91 936 2.07 968 2.23 998 2.39 1027 2.55 1058 2.73 1091 2.93 1124 3.14 1158 3.36 1189 3.57<br />

4400 986 2.50 1016 2.68 1047 2.86 1075 3.03 1101 3.20 1128 3.39 1155 3.58 1186 3.80 1217 4.03 1246 4.25<br />

4800 1070 3.22 1098 3.40 1127 3.60 1153 3.79 1178 3.98 1203 4.17 1227 4.37 1251 4.57 1279 4.80 1307 5.05<br />

5-HP Oversized Motor & Drive<br />

3-HP Standard Motor& Drive<br />

Table PD-84 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

3-HP Standard Motor & Drive<br />

3200 1090 2.53 1115 2.67 1139 2.81 1161 2.95 1183 3.09 1205 3.23 1225 3.37 1246 3.51 1265 3.65 1284 3.78<br />

3600 1157 3.13 1181 3.29 1205 3.45 1228 3.61 1250 3.77 1272 3.93 1293 4.09 1312 4.24 1331 4.40 1351 4.56<br />

4000 1218 3.78 1246 3.99 1271 4.18 1294 4.36 1317 4.55 1338 4.72 1360 4.91 1379 5.07 1398 5.25 1418 5.43<br />

4400 1276 4.49 1304 4.73 1333 4.97 1359 5.20 1383 5.42 1405 5.62 — — — — — — — —<br />

4800 1336 5.30 1363 5.56 — — — — — — — — — — — — — — — —<br />

5-HP Oversized Motor & Drive<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.<br />

5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.<br />

1. Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required.<br />

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full<br />

horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />

Table PD-85 — Belt Drive Evaporator Fan Performance — 10-Ton — YHC120A3,A4,AW *H— High Heat —Horizontal Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

3-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

3-HP Standard Motor & Drive<br />

3200 785 1.18 821 1.31 861 1.46 903 1.62 944 1.80 981 1.96 1014 2.12 1043 2.27 1070 2.41 1095 2.55<br />

3600 874 1.64 907 1.78 939 1.93 977 2.11 1014 2.30 1050 2.49 1084 2.69 1115 2.87 1144 3.05 1169 3.21<br />

4000 964 2.21 994 2.37 1023 2.53 1053 2.71 1087 2.91 1121 3.12 1154 3.33 1185 3.55 1215 3.76 1242 3.96<br />

4400 1055 2.91 1082 3.08 1109 3.25 1135 3.43 1164 3.64 1194 3.86 1225 4.09 1255 4.32 1284 4.56 1312 4.79<br />

4800 1146 3.74 1171 3.92 1196 4.11 1220 4.31 1244 4.51 1271 4.73 1298 4.97 1327 5.22 1354 5.47 1382 5.74<br />

5-HP Oversized Motor & Drive<br />

Table PD-85 — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

3-HP Standard Motor & Drive<br />

3200 1120 2.70 1143 2.84 1166 2.98 1188 3.12 1208 3.25 1229 3.39 1249 3.53 1269 3.67 1289 3.82 1308 3.96<br />

3600 1194 3.37 1217 3.53 1240 3.69 1262 3.85 1282 4.01 1303 4.17 1322 4.32 1341 4.48 1361 4.64 1378 4.79<br />

4000 1269 4.16 1292 4.34 1314 4.52 1335 4.70 1356 4.88 1377 5.06 1397 5.24 1415 5.41 — — — —<br />

4400 1339 5.02 1365 5.25 1388 5.47 1410 5.67 — — — — — — — — — — — —<br />

4800 — — — — — — — — — — — — — — — — — — — —<br />

5-HP Oversized Motor & Drive<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories<br />

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.<br />

5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.<br />

1. Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required<br />

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full<br />

horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.<br />