For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop<br />

due to other options/accessories<br />

F1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.<br />

2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000.<br />

RT-PRC006-EN<br />

Performance<br />

Data<br />

1. Field Supplied Fan Sheave AK84 and Belt AX34 required.<br />

Factory supplied motors, in commercial equipment, are<br />

definite purpose motors, specifically designed and tested to<br />

operate reliably and continuously at all cataloged conditions.<br />

Using the full horsepower range of our fan motors as shown in<br />

our tabular data will not result in nuisance tripping or<br />

premature motor failure. Our product’s warranty will not be<br />

affected.<br />

(6 Ton)<br />

Standard Efficiency<br />

Table PD-36 — Belt Drive Evaporator Fan Performance — 6 Ton — YSC072A3,A4,AW *L,M — Low and Medium Heat —Horizontal Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

1-HP Standard Motor & Drive<br />

1920 — — 576 0.32 636 0.40 687 0.46 733 0.54 778 0.62 821 0.70 864 0.78 906 0.86 946 0.95<br />

2160 575 0.37 619 0.43 674 0.50 726 0.59 770 0.66 812 0.74 852 0.82 890 0.92 930 1.01 968 1.10<br />

2400 629 0.49 669 0.55 713 0.62 763 0.71 809 0.81 849 0.89 887 0.97 923 1.06 959 1.16 994 1.27<br />

2640 684 0.63 721 0.71 757 0.78 802 0.86 846 0.96 888 1.07 925 1.16 959 1.25 993 1.34 1027 1.45<br />

2880 740 0.80 774 0.89 807 0.97 843 1.05 885 1.14 925 1.26 964 1.38 998 1.48 1030 1.57 1062 1.67<br />

2-HP Oversized<br />

Motor and Drive<br />

Table PD-36 — Continued<br />

1-HP Standard Motor & High Static Drive (or 2-HP Oversized Motor)<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard 1-HP Standard Motor & High Static Drive Kit<br />

Motor & Drive (or 2 HP Oversized Motor & Drive)<br />

1920 985 1.04 1020 1.13 1057 1.22 1090 1.31 1123 1.41 1155 1.50 1185 1.60 1213 1.69 1241 1.79 1268 1.88<br />

2160 1005 1.19 1040 1.29 1075 1.38 1110 1.48 1143 1.59 1176 1.69 1206 1.80 1235 1.90 1264 2.00 — —<br />

2400 1029 1.37 1063 1.47 1098 1.58 1130 1.68 1162 1.78 1194 1.89 1223 2.00 1254 2.11 — — — —<br />

2540 1058 1.56 1090 1.68 1121 1.79 1152 1.90 1184 2.01 1214 2.13 1244 2.24 — — — — — —<br />

2880 1093 1.78 1123 1.90 1152 2.02 1181 2.14 1211 2.27 — — — — — — — — — —<br />

2-HP Oversized Motor & Drive<br />

Table PD-37 — Belt Drive Evaporator Fan Performance — 6 Ton — YSC072A3,A4,AW *H — High Heat —Horizontal Airflow<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard Motor & Field Supplied<br />

Low Static Drive (1)<br />

1-HP Standard Motor & Drive<br />

1920 551 0.30 613 0.37 668 0.44 715 0.51 761 0.58 804 0.67 847 0.75 890 0.83 930 0.92 969 1.00<br />

2160 608 0.41 661 0.48 714 0.56 760 0.64 802 0.72 842 0.80 882 0.90 920 0.99 958 1.08 996 1.17<br />

2400 667 0.55 710 0.62 760 0.71 806 0.80 847 0.88 885 0.96 921 1.06 957 1.16 992 1.27 1027 1.37<br />

2640 726 0.72 762 0.79 809 0.87 853 0.98 894 1.09 930 1.17 965 1.26 998 1.36 1031 1.47 1063 1.58<br />

2880 786 0.91 818 0.99 857 1.08 900 1.18 939 1.30 976 1.41 1009 1.51 1042 1.61 1073 1.71 1103 1.82<br />

Table PD-37 — Continued<br />

2-HP Oversized Motor & Drive<br />

1-HP Standard Motor & High Static Drive (or 2-HP Oversized Motor)<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

1-HP Standard Motor & High Static Drive<br />

Kit (or 2 HP Oversized Motor & Drive)<br />

1920 1007 1.09 1044 1.19 1078 1.28 1111 1.37 1142 1.46 1172 1.56 1203 1.65 1230 1.75 1257 1.84 — —<br />

2160 1032 1.26 1068 1.36 1102 1.46 1135 1.56 1167 1.66 1198 1.77 1229 1.88 1259 1.98 — — — —<br />

2400 1061 1.47 1095 1.57 1128 1.67 1161 1.78 1191 1.88 1223 2.00 1254 2.11 1282 2.23 — — — —<br />

2640 1095 1.70 1126 1.81 1157 1.92 1189 2.03 1219 2.15 1250 2.26 — — — — — — — —<br />

2880 1133 1.94 1162 2.06 1191 2.19 1221 2.30 — — — — — — — — — — — —<br />

2-HP Oversized Motor & Drive<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-86.<br />

Notes:<br />

Data includes pressure drop due to standard filters and wet coils.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-89 to determine additional static pressure drop<br />

due to other options/accessories<br />

1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.<br />

2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000<br />

1. Field Supplied Fan Sheave AK84 and Belt AX34 required.<br />

Factory supplied motors, in commercial equipment, are<br />

definite purpose motors, specifically designed and<br />

tested to operate reliably and continuously at all<br />

cataloged conditions. Using the full horsepower range<br />

of our fan motors as shown in our tabular data will not<br />

result in nuisance tripping or premature motor failure.<br />

Our product’s warranty will not be affected.<br />