9<br />

Communication<br />

Industrial Ethernet<br />

<strong>System</strong> connection <strong>PCS</strong> 7 systems<br />

■ Design<br />

Connection of single stations, servers and clients<br />

<strong>SIMATIC</strong> <strong>PCS</strong> 7 subsystems for engineering, operation and<br />

monitoring (also via Internet/Intranet), batch control, route control,<br />

asset management or IT applications are distributed between<br />

various <strong>SIMATIC</strong> <strong>PCS</strong> 7 Industrial Workstations of single<br />

station, server or client design depending on the configuration.<br />

Depending on their task and the associated integration into<br />

the complete system, these <strong>SIMATIC</strong> <strong>PCS</strong> 7 Industrial<br />

Workstations are connected either only on the plant bus, only<br />

on the OS LAN (terminal bus) or on both buses of the Industrial<br />

Ethernet network. The redundant or non-redundant connection<br />

is made using onboard interfaces, simple network cards or special<br />

communications processors (e.g. CP 1613).<br />

CP 1613<br />

Connection to plant bus<br />

Single stations and servers can be operated on the plant bus via<br />

Basic Communication Ethernet (network card plus BCE license)<br />

or CP 1613 communication. CP 1613 communication is always<br />

required for ES/OS single stations and OS servers if an operator<br />

system has more than 8 subordinate automation systems or if<br />

fault-tolerant automation systems are used. In all other cases,<br />

the more cost-effective Basic Communication Ethernet (BCE)<br />

can be used instead.<br />

BCE and CP 1613 communication is embedded in each case in<br />

an alternative <strong>SIMATIC</strong> <strong>PCS</strong> 7 Workstation for single station and<br />

server.<br />

The separately available desktop adapter network card can also<br />

be used for BCE. The BCE license is already included with SI-<br />

MATIC <strong>PCS</strong> 7 Workstations. If you use alternative hardware instead<br />

for your stations, you require an additional BCE license for<br />

each station which communicates over the plant bus via BCE.<br />

9/28<br />

<strong>Siemens</strong> ST <strong>PCS</strong> 7 · November 2007<br />

© <strong>Siemens</strong> AG 2007<br />

The CP 1613 communication delivered with <strong>SIMATIC</strong> <strong>PCS</strong> 7<br />

Workstations for single stations and servers instead of BCE is<br />

a combination of CP 1613 communications processor and<br />

S7-1613 communications software. However, if fault-tolerant<br />

automation systems are used, ES/OS single stations and<br />

OS servers require the S7-REDCONNECT software instead of<br />

the S7-1613 communications software. ES/OS single stations<br />

and OS servers with S7-1613 communications software can be<br />

accordingly upgraded in this case using the S7-REDCONNECT<br />

Upgrade (see also page 9/28).<br />

Single stations and servers with BCE can also be subsequently<br />

upgraded to CP 1613 communication. Depending on the abovementioned<br />

criteria, either the S7-1613 communications software<br />

or the S7-REDCONNECT software is required in addition to the<br />

CP 1613 communications processor.<br />

Connection to OS LAN (terminal bus)<br />

<strong>SIMATIC</strong> <strong>PCS</strong> 7 Industrial Workstations in client, server or single<br />

station designs are connected as standard to the OS LAN via the<br />

onboard Industrial Ethernet interface. In the case of servers or<br />

single stations without a connection to the plant bus, the network<br />

card envisaged for BCE can be used as an alternative.<br />

The OS LAN can also have a redundant configuration, where two<br />

rings are connected together via two pairs of switches (see also<br />

"Introduction" at the beginning of the catalog section on Industrial<br />

Ethernet). A "<strong>SIMATIC</strong> <strong>PCS</strong> 7 Redundant Terminal Bus<br />

Adapter Package", comprising server and desktop adapter network<br />

cards, is required to connect the stations to the two rings of<br />

the redundant OS LAN.<br />

Connection of automation systems<br />

The <strong>SIMATIC</strong> <strong>PCS</strong> 7 automation systems communicate with<br />

other subsystems of the process control system (e.g. operator<br />

system or engineering system) via the Industrial Ethernet plant<br />

bus. The automation systems are connected to the plant bus using<br />

the CP 443-1 communications processor, also redundant in<br />

the case of fault-tolerant systems.