■ Design<br />
Connection of single stations, servers and clients<br />
<strong>SIMATIC</strong> <strong>PCS</strong> 7 subsystems for engineering, operation and<br />
monitoring (also via Internet/Intranet), batch control, route control,<br />
asset management or IT applications are distributed between<br />
various <strong>SIMATIC</strong> <strong>PCS</strong> 7 Industrial Workstations of single<br />
station, server or client design depending on the configuration.<br />
Depending on their task and the associated integration into<br />
the complete system, these <strong>SIMATIC</strong> <strong>PCS</strong> 7 Industrial<br />
Workstations are connected either only on the plant bus, only<br />
on the OS LAN (terminal bus) or on both buses of the Industrial<br />
Ethernet network. The redundant or non-redundant connection<br />
is made using onboard interfaces, simple network cards or special<br />
communications processors (e.g. CP 1613).<br />
CP 1613<br />
Connection to plant bus<br />
Single stations and servers can be operated on the plant bus via<br />
Basic Communication Ethernet (network card plus BCE license)<br />
or CP 1613 communication. CP 1613 communication is always<br />
required for ES/OS single stations and OS servers if an operator<br />
system has more than 8 subordinate automation systems or if<br />
fault-tolerant automation systems are used. In all other cases,<br />
the more cost-effective Basic Communication Ethernet (BCE)<br />
can be used instead.<br />
BCE and CP 1613 communication is embedded in each case in<br />
an alternative <strong>SIMATIC</strong> <strong>PCS</strong> 7 Workstation for single station and<br />
server.<br />
The separately available desktop adapter network card can also<br />
be used for BCE. The BCE license is already included with SI-<br />
MATIC <strong>PCS</strong> 7 Workstations. If you use alternative hardware instead<br />
for your stations, you require an additional BCE license for<br />
each station which communicates over the plant bus via BCE.<br />
9/28<br />
<strong>Siemens</strong> ST <strong>PCS</strong> 7 · November 2007<br />
© <strong>Siemens</strong> AG 2007<br />
The CP 1613 communication delivered with <strong>SIMATIC</strong> <strong>PCS</strong> 7<br />
Workstations for single stations and servers instead of BCE is<br />
a combination of CP 1613 communications processor and<br />
S7-1613 communications software. However, if fault-tolerant<br />
automation systems are used, ES/OS single stations and<br />
OS servers require the S7-REDCONNECT software instead of<br />
the S7-1613 communications software. ES/OS single stations<br />
and OS servers with S7-1613 communications software can be<br />
accordingly upgraded in this case using the S7-REDCONNECT<br />
Upgrade (see also page 9/28).<br />
Single stations and servers with BCE can also be subsequently<br />
upgraded to CP 1613 communication. Depending on the abovementioned<br />
criteria, either the S7-1613 communications software<br />
or the S7-REDCONNECT software is required in addition to the<br />
CP 1613 communications processor.<br />
Connection to OS LAN (terminal bus)<br />
<strong>SIMATIC</strong> <strong>PCS</strong> 7 Industrial Workstations in client, server or single<br />
station designs are connected as standard to the OS LAN via the<br />
onboard Industrial Ethernet interface. In the case of servers or<br />
single stations without a connection to the plant bus, the network<br />
card envisaged for BCE can be used as an alternative.<br />
The OS LAN can also have a redundant configuration, where two<br />
rings are connected together via two pairs of switches (see also<br />
"Introduction" at the beginning of the catalog section on Industrial<br />
Ethernet). A "<strong>SIMATIC</strong> <strong>PCS</strong> 7 Redundant Terminal Bus<br />
Adapter Package", comprising server and desktop adapter network<br />
cards, is required to connect the stations to the two rings of<br />
the redundant OS LAN.<br />
Connection of automation systems<br />
The <strong>SIMATIC</strong> <strong>PCS</strong> 7 automation systems communicate with<br />
other subsystems of the process control system (e.g. operator<br />
system or engineering system) via the Industrial Ethernet plant<br />
bus. The automation systems are connected to the plant bus using<br />
the CP 443-1 communications processor, also redundant in<br />
the case of fault-tolerant systems.