9<br />
Communication<br />
PROFIBUS PA<br />
Introduction<br />
■ Design<br />
Basic PROFIBUS PA design versions when using the DP/PA link as the<br />
router<br />
Basic PROFIBUS PA design versions are presented at this point.<br />
In these configuration examples, DP/PA links are used in each<br />
case as the DP/PA router. Up to 5 DP/PA couplers can be operated<br />
in a DP/PA link. Mixed configurations (e.g. line and ring on<br />
one link) are also possible. The DP/PA router can also be implemented<br />
with a DP/PA coupler. In this case, the PROFIBUS DP<br />
connection is directly on the coupler instead of per interface<br />
module.<br />
Linear architecture with single coupler<br />
In this design version, each PROFIBUS PA line is linked with one<br />
DP/PA coupler of a DP/PA router. Depending on the operating<br />
environment, you can use either the FDC 157-0 DP/PA coupler<br />
(up to Ex zone 2) or the Ex [i] DP/PA coupler (up to Ex zone 1).<br />
The DP/PA router can be connected to a single or redundant<br />
PROFIBUS DP.<br />
Linear architecture with redundant couplers<br />
The active field splitter (AFS) connects a PROFIBUS PA line with<br />
two FDC 157-0 DP/PA couplers of a DP/PA router. This router is<br />
operable on a single or redundant PROFIBUS DP. The AFS<br />
switches the PROFIBUS PA line to the active one of the two redundant<br />
couplers.<br />
Flexible Modular Redundancy is possible at the device level by<br />
grouping individual devices in different PROFIBUS PA lines.<br />
Only one PROFIBUS PA line can be configured with coupler redundancy<br />
on each DP/PA router. A PROFIBUS PA ring cannot<br />
then be operated on this router.<br />
9/44<br />
Direct fieldbus interfacing<br />
PROFIBUS DP<br />
AS 414FH/<br />
AS 417FH<br />
Active field<br />
splitter<br />
DP/PA Link<br />
Active field distributors<br />
PROFIBUS PA<br />
<strong>Siemens</strong> ST <strong>PCS</strong> 7 · November 2007<br />
PROFIBUS PA<br />
DP/PA Link<br />
with redundant DP/PA couplers<br />
PROFIBUS PA<br />
DP/PA Link<br />
with redundant DP/PA couplers<br />
© <strong>Siemens</strong> AG 2007<br />
Ring architecture<br />
Active field distributors (AFD) integrate PROFIBUS PA field<br />
devices via 4 short-circuit proof spur line connections into<br />
a PROFIBUS PA ring with automatic bus termination. The<br />
PROFIBUS PA ring is connected to two FDC 157-0 DP/PA couplers<br />
of a DP/PA router. The DP/PA router can be operated on a<br />
single or redundant PROFIBUS DP. Up to 8 AFDs can be configured<br />
per ring.<br />
Flexible Modular Redundancy is possible at the device level by<br />
grouping individual devices on different AFDs. Only one ring can<br />
be configured on each DP/PA router. A PROFIBUS PA line with<br />
coupler redundancy cannot then be operated on this router.<br />
The following limits must be observed for a PROFIBUS PA ring<br />
with respect to the configuration with PROFIBUS PA devices:<br />
• Max. 31 PROFIBUS-PA devices<br />
• Max. current consumption of all PROFIBUS-PA devices: 1 A<br />
Particular advantages of the ring architecture:<br />
• High availability<br />
• Transparent redundancy management of the intelligent<br />
FDC 157-0 DP/PA couplers for the higher-level system<br />
• Active bus terminations for automatic bus termination in the<br />
FDC 157-0 DP/PA couplers and the AFDs permit:<br />
- Automatic, bumpless isolation of defective sub-segments in<br />
event of short-circuit or wire breakage<br />
- Changing of the ring configuration and the instrumentation<br />
during operation, including addition or removal of ring segments<br />
• Safety-related and fault-tolerant applications with low device<br />
and cabling overheads<br />
■ Technical specifications<br />
PROFIBUS PA<br />
Data transmission MBP<br />
Transmission rate 31.25 Mbit/s<br />
Cable 2-wire shielded<br />
Type of protection EEx(ia/ib)<br />
Topology Line, tree, ring<br />
PA devices per segment/coupler 31<br />
PA devices per DP/PA link 64<br />
Cable length per segment depen- 1900 m: standard<br />
dent on transmission rate<br />
1900 m: EEx(ib)<br />
1000 m: EEx(ia)