9<br />

Communication<br />

PROFIBUS PA<br />

Introduction<br />

■ Design<br />

Basic PROFIBUS PA design versions when using the DP/PA link as the<br />

router<br />

Basic PROFIBUS PA design versions are presented at this point.<br />

In these configuration examples, DP/PA links are used in each<br />

case as the DP/PA router. Up to 5 DP/PA couplers can be operated<br />

in a DP/PA link. Mixed configurations (e.g. line and ring on<br />

one link) are also possible. The DP/PA router can also be implemented<br />

with a DP/PA coupler. In this case, the PROFIBUS DP<br />

connection is directly on the coupler instead of per interface<br />

module.<br />

Linear architecture with single coupler<br />

In this design version, each PROFIBUS PA line is linked with one<br />

DP/PA coupler of a DP/PA router. Depending on the operating<br />

environment, you can use either the FDC 157-0 DP/PA coupler<br />

(up to Ex zone 2) or the Ex [i] DP/PA coupler (up to Ex zone 1).<br />

The DP/PA router can be connected to a single or redundant<br />

PROFIBUS DP.<br />

Linear architecture with redundant couplers<br />

The active field splitter (AFS) connects a PROFIBUS PA line with<br />

two FDC 157-0 DP/PA couplers of a DP/PA router. This router is<br />

operable on a single or redundant PROFIBUS DP. The AFS<br />

switches the PROFIBUS PA line to the active one of the two redundant<br />

couplers.<br />

Flexible Modular Redundancy is possible at the device level by<br />

grouping individual devices in different PROFIBUS PA lines.<br />

Only one PROFIBUS PA line can be configured with coupler redundancy<br />

on each DP/PA router. A PROFIBUS PA ring cannot<br />

then be operated on this router.<br />

9/44<br />

Direct fieldbus interfacing<br />

PROFIBUS DP<br />

AS 414FH/<br />

AS 417FH<br />

Active field<br />

splitter<br />

DP/PA Link<br />

Active field distributors<br />

PROFIBUS PA<br />

<strong>Siemens</strong> ST <strong>PCS</strong> 7 · November 2007<br />

PROFIBUS PA<br />

DP/PA Link<br />

with redundant DP/PA couplers<br />

PROFIBUS PA<br />

DP/PA Link<br />

with redundant DP/PA couplers<br />

© <strong>Siemens</strong> AG 2007<br />

Ring architecture<br />

Active field distributors (AFD) integrate PROFIBUS PA field<br />

devices via 4 short-circuit proof spur line connections into<br />

a PROFIBUS PA ring with automatic bus termination. The<br />

PROFIBUS PA ring is connected to two FDC 157-0 DP/PA couplers<br />

of a DP/PA router. The DP/PA router can be operated on a<br />

single or redundant PROFIBUS DP. Up to 8 AFDs can be configured<br />

per ring.<br />

Flexible Modular Redundancy is possible at the device level by<br />

grouping individual devices on different AFDs. Only one ring can<br />

be configured on each DP/PA router. A PROFIBUS PA line with<br />

coupler redundancy cannot then be operated on this router.<br />

The following limits must be observed for a PROFIBUS PA ring<br />

with respect to the configuration with PROFIBUS PA devices:<br />

• Max. 31 PROFIBUS-PA devices<br />

• Max. current consumption of all PROFIBUS-PA devices: 1 A<br />

Particular advantages of the ring architecture:<br />

• High availability<br />

• Transparent redundancy management of the intelligent<br />

FDC 157-0 DP/PA couplers for the higher-level system<br />

• Active bus terminations for automatic bus termination in the<br />

FDC 157-0 DP/PA couplers and the AFDs permit:<br />

- Automatic, bumpless isolation of defective sub-segments in<br />

event of short-circuit or wire breakage<br />

- Changing of the ring configuration and the instrumentation<br />

during operation, including addition or removal of ring segments<br />

• Safety-related and fault-tolerant applications with low device<br />

and cabling overheads<br />

■ Technical specifications<br />

PROFIBUS PA<br />

Data transmission MBP<br />

Transmission rate 31.25 Mbit/s<br />

Cable 2-wire shielded<br />

Type of protection EEx(ia/ib)<br />

Topology Line, tree, ring<br />

PA devices per segment/coupler 31<br />

PA devices per DP/PA link 64<br />

Cable length per segment depen- 1900 m: standard<br />

dent on transmission rate<br />

1900 m: EEx(ib)<br />

1000 m: EEx(ia)