11<br />
<strong>Process</strong> I/O<br />
ET 200S distributed I/O<br />
Motor starters<br />
High Feature motor starters<br />
The High Feature motor starters are used together with the PM-D<br />
power module. Combined with a terminal module according to<br />
the table, a PM-D power module opens up a new potential<br />
group. The scope of the group is limited in that the value specified<br />
for the current carrying capacity of the power module (10 A<br />
for PM-D) must not be exceeded by the total current of all modules<br />
in a potential group.<br />
The PM-D handles the following tasks for the motor starters in a<br />
potential group:<br />
• Supply of voltages for the electronics via the voltage buses of<br />
the terminal modules<br />
• Monitoring of voltages for the electronics and contactors<br />
With power bus supply<br />
for one load group,<br />
including 3 caps for termination<br />
of power bus<br />
Safety-oriented motor starters<br />
In EMERGENCY STOP applications, safety-oriented motor starters<br />
can be shut down selectively by means of the upstream<br />
PM-D F PROFIsafe power module. Up to 6 shut-down groups<br />
can be formed per power module. The PM-D F PROFIsafe obtains<br />
the shut-down signal from the F/FH automation system via<br />
the interface module of the ET 200S.<br />
Combined with a terminal module according to the table, a<br />
PM-D F PROFIsafe power module opens up a new potential<br />
group. The scope of the group is limited in that the total current<br />
of all modules in a potential group must not exceed the current<br />
carrying capacity of the power module (with PM-D F PROFIsafe:<br />
inrush current 10 A; continuous current 5 A).<br />
11/50<br />
Terminal modules for<br />
motor starters and power modules<br />
TM-DS65-<br />
S32<br />
3RK1 903-<br />
0AK00<br />
With power bus bushing TM-DS65-<br />
S31<br />
3RK1 903-<br />
0AK10<br />
TM-RS130-<br />
S32<br />
3RK1 903-<br />
0AL00<br />
TM-RS130-<br />
S31<br />
3RK1 903-<br />
0AL10<br />
With screw terminals<br />
Power module<br />
-- -- TM-P15-S27-<br />
01<br />
3RK1 903-<br />
0AA00<br />
PM-D 24 V DC<br />
Motor starters<br />
•<br />
DS1e-x<br />
High Feature direct-online<br />
starter<br />
•<br />
DSS1e-x<br />
High Feature direct-online<br />
soft starter<br />
•<br />
RS1e-x<br />
High Feature reversing<br />
starter<br />
•<br />
<strong>Siemens</strong> ST <strong>PCS</strong> 7 · November 2007<br />
© <strong>Siemens</strong> AG 2007<br />
--<br />
--<br />
With power bus supply<br />
for one load group,<br />
including 3 caps for<br />
termination of power bus<br />
Terminal modules for motor<br />
starters, power modules and<br />
supplementary/expansion modules<br />
TM-FD65-<br />
S32<br />
3RK1 903-<br />
3AC00<br />
With power bus bushing TM-FD65-<br />
S31<br />
3RK1 903-<br />
3AC10<br />
TM-FRS130-<br />
S32<br />
3RK1 903-<br />
3AD00<br />
TM-FRS130-<br />
S31<br />
3RK1 903-<br />
3AD10<br />
With screw terminals<br />
Power module<br />
-- -- TM-<br />
PF30S47-F0<br />
3RK1 903-<br />
3AA00<br />
PM-D F PROFIsafe<br />
Motor starters<br />
•<br />
F-DS1e-x<br />
High Feature<br />
direct-on-line starter<br />
•<br />
F-RS1e-x<br />
High Feature reversing<br />
starter<br />
•<br />
Supplementary/expansion modules for safety-oriented motor<br />
starter applications<br />
The PM-D F X1 power/expansion module permits selective shutdown<br />
of 1 to 6 shut-down groups through external safety devices<br />
(e.g. safety relay or AS-i safety monitor). The PM-D F X1<br />
uses the safety-oriented shut-down signals connected to the<br />
module to trigger the downstream failsafe motor starters which<br />
then safely switch off the assigned motors.<br />
In addition, external safety devices can also be powered by a<br />
safe 24 V DC voltage V1 via the safety-oriented PM-D F X1<br />
power/expansion module.<br />
The F-CM contact multiplier equipped with four safe floating<br />
contacts (NO contacts) can be used together with the PM-D F<br />
PROFIsafe or the PM-D F X1 as an interface to plants with conventional<br />
safety engineering. It has internal diagnostics functions,<br />
and can be set to one of 6 shut-down groups.<br />
Without supply from left<br />
(as power module)<br />
With supply from left<br />
(for expansion)<br />
Additional/expansion modules<br />
PM-D F X1<br />
safety-oriented power/<br />
expansion module<br />
F-CM<br />
safety-oriented contact<br />
multiplier<br />
Terminal modules for<br />
supplementary/expansion modules<br />
TM-PFX30 S47- --<br />
G1<br />
3RK1 903-3AE00<br />
TM-PFX30 S47- --<br />
G0<br />
3RK1 903-3AE10<br />
-- TM-FCM30-S47<br />
3RK1 903-3AB10<br />
•<br />