11<br />

<strong>Process</strong> I/O<br />

ET 200S distributed I/O<br />

Motor starters<br />

High Feature motor starters<br />

The High Feature motor starters are used together with the PM-D<br />

power module. Combined with a terminal module according to<br />

the table, a PM-D power module opens up a new potential<br />

group. The scope of the group is limited in that the value specified<br />

for the current carrying capacity of the power module (10 A<br />

for PM-D) must not be exceeded by the total current of all modules<br />

in a potential group.<br />

The PM-D handles the following tasks for the motor starters in a<br />

potential group:<br />

• Supply of voltages for the electronics via the voltage buses of<br />

the terminal modules<br />

• Monitoring of voltages for the electronics and contactors<br />

With power bus supply<br />

for one load group,<br />

including 3 caps for termination<br />

of power bus<br />

Safety-oriented motor starters<br />

In EMERGENCY STOP applications, safety-oriented motor starters<br />

can be shut down selectively by means of the upstream<br />

PM-D F PROFIsafe power module. Up to 6 shut-down groups<br />

can be formed per power module. The PM-D F PROFIsafe obtains<br />

the shut-down signal from the F/FH automation system via<br />

the interface module of the ET 200S.<br />

Combined with a terminal module according to the table, a<br />

PM-D F PROFIsafe power module opens up a new potential<br />

group. The scope of the group is limited in that the total current<br />

of all modules in a potential group must not exceed the current<br />

carrying capacity of the power module (with PM-D F PROFIsafe:<br />

inrush current 10 A; continuous current 5 A).<br />

11/50<br />

Terminal modules for<br />

motor starters and power modules<br />

TM-DS65-<br />

S32<br />

3RK1 903-<br />

0AK00<br />

With power bus bushing TM-DS65-<br />

S31<br />

3RK1 903-<br />

0AK10<br />

TM-RS130-<br />

S32<br />

3RK1 903-<br />

0AL00<br />

TM-RS130-<br />

S31<br />

3RK1 903-<br />

0AL10<br />

With screw terminals<br />

Power module<br />

-- -- TM-P15-S27-<br />

01<br />

3RK1 903-<br />

0AA00<br />

PM-D 24 V DC<br />

Motor starters<br />

•<br />

DS1e-x<br />

High Feature direct-online<br />

starter<br />

•<br />

DSS1e-x<br />

High Feature direct-online<br />

soft starter<br />

•<br />

RS1e-x<br />

High Feature reversing<br />

starter<br />

•<br />

<strong>Siemens</strong> ST <strong>PCS</strong> 7 · November 2007<br />

© <strong>Siemens</strong> AG 2007<br />

--<br />

--<br />

With power bus supply<br />

for one load group,<br />

including 3 caps for<br />

termination of power bus<br />

Terminal modules for motor<br />

starters, power modules and<br />

supplementary/expansion modules<br />

TM-FD65-<br />

S32<br />

3RK1 903-<br />

3AC00<br />

With power bus bushing TM-FD65-<br />

S31<br />

3RK1 903-<br />

3AC10<br />

TM-FRS130-<br />

S32<br />

3RK1 903-<br />

3AD00<br />

TM-FRS130-<br />

S31<br />

3RK1 903-<br />

3AD10<br />

With screw terminals<br />

Power module<br />

-- -- TM-<br />

PF30S47-F0<br />

3RK1 903-<br />

3AA00<br />

PM-D F PROFIsafe<br />

Motor starters<br />

•<br />

F-DS1e-x<br />

High Feature<br />

direct-on-line starter<br />

•<br />

F-RS1e-x<br />

High Feature reversing<br />

starter<br />

•<br />

Supplementary/expansion modules for safety-oriented motor<br />

starter applications<br />

The PM-D F X1 power/expansion module permits selective shutdown<br />

of 1 to 6 shut-down groups through external safety devices<br />

(e.g. safety relay or AS-i safety monitor). The PM-D F X1<br />

uses the safety-oriented shut-down signals connected to the<br />

module to trigger the downstream failsafe motor starters which<br />

then safely switch off the assigned motors.<br />

In addition, external safety devices can also be powered by a<br />

safe 24 V DC voltage V1 via the safety-oriented PM-D F X1<br />

power/expansion module.<br />

The F-CM contact multiplier equipped with four safe floating<br />

contacts (NO contacts) can be used together with the PM-D F<br />

PROFIsafe or the PM-D F X1 as an interface to plants with conventional<br />

safety engineering. It has internal diagnostics functions,<br />

and can be set to one of 6 shut-down groups.<br />

Without supply from left<br />

(as power module)<br />

With supply from left<br />

(for expansion)<br />

Additional/expansion modules<br />

PM-D F X1<br />

safety-oriented power/<br />

expansion module<br />

F-CM<br />

safety-oriented contact<br />

multiplier<br />

Terminal modules for<br />

supplementary/expansion modules<br />

TM-PFX30 S47- --<br />

G1<br />

3RK1 903-3AE00<br />

TM-PFX30 S47- --<br />

G0<br />

3RK1 903-3AE10<br />

-- TM-FCM30-S47<br />

3RK1 903-3AB10<br />

•<br />

•<br />

--<br />

--