SIMATIC PCS 7 Process Control System - Siemens
SIMATIC PCS 7 Process Control System - Siemens
SIMATIC PCS 7 Process Control System - Siemens
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
© <strong>Siemens</strong> AG 2007<br />
<strong>Process</strong> I/O<br />
ET 200M distributed I/O<br />
AO - analog output modules<br />
■ Overview<br />
■ Selection and Ordering Data Order No.<br />
SM 332 modules for current and voltage outputs<br />
2 outputs in 2 channel groups<br />
• Resolution 12 bit + sign<br />
• Voltage 0/1 to 5/10 V; ±10 V<br />
(2 channels; 2 or 4 wires)<br />
• Current 0/4 to 20 mA; ±20 mA<br />
(2 channels; 2 wires)<br />
• Parameterizable substitute value<br />
output in case of CPU stop<br />
• Broken wire monitoring (only for<br />
current)<br />
• Short circuit monitoring (only for<br />
voltage)<br />
• Diagnostics inside module<br />
• Front connector required:<br />
20-contact<br />
6ES7 332-5HB01-0AB0<br />
4 outputs in 4 channel groups<br />
Redundant design possible<br />
6ES7 332-5HD01-0AB0<br />
The analog output modules for voltage and current described (module redundancy)<br />
here break down into<br />
• Resolution 12 bit + sign<br />
• modules with 12 bit resolution and various numbers of chan- • Voltage 0/1 to 5/10 V; ±10 V<br />
nels, and<br />
(4 channels; 4 wires)<br />
• a high-precision module with 15 bit resolution.<br />
The analog output modules can be parameterized in groups independently<br />
of each other and automatically supply all channelspecific<br />
and module-internal diagnostics data.<br />
• Current 0/4 to 20 mA; ±20 mA<br />
(4 channels; 2 wires)<br />
• Parameterizable substitute value<br />
output in case of CPU stop<br />
• Broken wire monitoring (only for<br />
current)<br />
• Short circuit monitoring (only for<br />
voltage)<br />
• Diagnostics inside module<br />
• Front connector required:<br />
20-contact<br />
8 outputs in 8 channel groups<br />
Redundant design possible<br />
(module and channel redundancy)<br />
• Resolution 12 bit + sign<br />
• Voltage 0/1 to 5/10 V; ±10 V<br />
(8 channels; 4 wires)<br />
• Current 0/4 to 20 mA; ±20 mA<br />
(8 channels; 2 wires)<br />
• Parameterizable substitute value<br />
output in case of CPU stop<br />
• Broken wire monitoring (only for<br />
current)<br />
• Short circuit monitoring (only for<br />
voltage)<br />
• Diagnostics inside module<br />
• Front connector required:<br />
40-contact<br />
6ES7 332-5HF00-0AB0<br />
4 outputs in 4 channel groups<br />
• Resolution 15 bit + sign<br />
• Voltage 0/1 to 5/10 V; ±10 V<br />
(4 channels; 4 wires)<br />
• Current 0/4 to 20 mA; ±20 mA<br />
(4 channels; 2 wires)<br />
• Parameterizable substitute value<br />
output in case of CPU stop<br />
• Isolated by channel<br />
• Diagnostics inside module<br />
• Front connector required:<br />
20-contact<br />
6ES7 332-7ND02-0AB0 B)<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
<strong>Siemens</strong> ST <strong>PCS</strong> 7 · November 2007<br />
11/21<br />
11