■ Overview<br />
The following analog electronics modules can be used for connecting<br />
actuators/sensors in the context of <strong>SIMATIC</strong> <strong>PCS</strong> 7:<br />
Analog input modules<br />
EM 4 AI U High Feature<br />
• 4 inputs for voltage measurements<br />
• Input ranges:<br />
- ± 10 V, resolution 15 bit + sign<br />
- ± 5 V, resolution 15 bit + sign<br />
- 0 to 10 V, resolution 15 bit<br />
- 1 to 5 V, resolution 15 bit<br />
• Electrically isolated from load voltage 2L+<br />
• Diagnostics "Short-circuit of sensor supply to M" per module<br />
• Diagnostics "Short-circuit, open-circuit" per channel (depending<br />
on measuring range)<br />
• <strong>Process</strong> interrupt with limit violation on channel 0<br />
• Permissible common-mode voltage 5 Vpp AC<br />
EM 4 AI I High Feature<br />
• 4 inputs for current measurements<br />
• Input ranges:<br />
- ± 20 mA, resolution 15 bit + sign<br />
- 0 to 20 mA, resolution 15 bit<br />
- 4 to 20 mA, resolution 15 bit<br />
• Two-wire and four-wire transmitters can be connected<br />
• Electrically isolated from load voltage 2L+<br />
• Diagnostics "Short-circuit of sensor supply to M" per module<br />
• Diagnostics "Short-circuit, open-circuit" per channel (depending<br />
on measuring range)<br />
• <strong>Process</strong> interrupt with limit violation on channel 0<br />
• Permissible common-mode voltage 5 Vpp AC<br />
© <strong>Siemens</strong> AG 2007<br />
<strong>Process</strong> I/O<br />
Dezentrale Peripherie ET 200pro<br />
Analog electronics modules EM 144, EM 145<br />
EM 4 AI RTD High Feature<br />
• 4 inputs for isolated (floating) resistance measurements or<br />
resistance thermometers with 2-, 3- and 4-wire connections<br />
• Input ranges:<br />
- Resistance measurement: 150 Ω; 300 Ω; 600 Ω; 3000 Ω;<br />
resolution 15 bit<br />
- Resistance thermometer: Pt100; Ni100; Ni120; Pt200; Ni200;<br />
Pt500; Ni500; Pt1000; Ni1000; resolution 15 bit + sign<br />
• Automatic compensation of line resistances with 3- and 4-wire<br />
connections<br />
• Parameterizable temperature coefficient with resistance-type<br />
sensors<br />
• Electrically isolated from load voltage supply 1L+ and 2L+<br />
• Linearization of sensor characteristics<br />
• Diagnostics "Open-circuit" per channel (terminals 1 and 3 are<br />
monitored for open-circuit)<br />
• Permissible common-mode voltage 10 Vpp AC<br />
Analog output modules<br />
EM 4 AO U High Feature<br />
• 4 outputs for voltage output<br />
• Output ranges:<br />
- ± 10 V, resolution 15 bit + sign<br />
- 1 to 5 V, resolution 14 bit<br />
- 0 to 10 V, resolution 15 bit<br />
• Electrically isolated from sensor supply voltage 1L+<br />
• Diagnostics "Short-circuit of sensor supply to M" per module<br />
• Diagnostics "Open-circuit in outputs" per channel<br />
• Substitute value output<br />
EM 4 AO I High Feature<br />
• 4 outputs for current output<br />
• Output ranges:<br />
- ± 20 mA, resolution 15 bit + sign<br />
- 4 to 20 mA, resolution 14 bit<br />
- 0 to 20 mA, resolution 15 bit<br />
• Electrically isolated from sensor supply voltage 1L+<br />
• Diagnostics "Short-circuit of sensor supply to M" per module<br />
• Diagnostics "Open-circuit" per channel<br />
• Substitute value output<br />
■ Technical specifications<br />
For detailed technical specifications of the analog electronics<br />
modules, see:<br />
• Catalog IK PI<br />
• Mall/CA 01 under "Distributed I/Os / ET 200pro"<br />
<strong>Siemens</strong> ST <strong>PCS</strong> 7 · November 2007<br />
11/61<br />
11