■ Overview<br />

The following analog electronics modules can be used for connecting<br />

actuators/sensors in the context of <strong>SIMATIC</strong> <strong>PCS</strong> 7:<br />

Analog input modules<br />

EM 4 AI U High Feature<br />

• 4 inputs for voltage measurements<br />

• Input ranges:<br />

- ± 10 V, resolution 15 bit + sign<br />

- ± 5 V, resolution 15 bit + sign<br />

- 0 to 10 V, resolution 15 bit<br />

- 1 to 5 V, resolution 15 bit<br />

• Electrically isolated from load voltage 2L+<br />

• Diagnostics "Short-circuit of sensor supply to M" per module<br />

• Diagnostics "Short-circuit, open-circuit" per channel (depending<br />

on measuring range)<br />

• <strong>Process</strong> interrupt with limit violation on channel 0<br />

• Permissible common-mode voltage 5 Vpp AC<br />

EM 4 AI I High Feature<br />

• 4 inputs for current measurements<br />

• Input ranges:<br />

- ± 20 mA, resolution 15 bit + sign<br />

- 0 to 20 mA, resolution 15 bit<br />

- 4 to 20 mA, resolution 15 bit<br />

• Two-wire and four-wire transmitters can be connected<br />

• Electrically isolated from load voltage 2L+<br />

• Diagnostics "Short-circuit of sensor supply to M" per module<br />

• Diagnostics "Short-circuit, open-circuit" per channel (depending<br />

on measuring range)<br />

• <strong>Process</strong> interrupt with limit violation on channel 0<br />

• Permissible common-mode voltage 5 Vpp AC<br />

© <strong>Siemens</strong> AG 2007<br />

<strong>Process</strong> I/O<br />

Dezentrale Peripherie ET 200pro<br />

Analog electronics modules EM 144, EM 145<br />

EM 4 AI RTD High Feature<br />

• 4 inputs for isolated (floating) resistance measurements or<br />

resistance thermometers with 2-, 3- and 4-wire connections<br />

• Input ranges:<br />

- Resistance measurement: 150 Ω; 300 Ω; 600 Ω; 3000 Ω;<br />

resolution 15 bit<br />

- Resistance thermometer: Pt100; Ni100; Ni120; Pt200; Ni200;<br />

Pt500; Ni500; Pt1000; Ni1000; resolution 15 bit + sign<br />

• Automatic compensation of line resistances with 3- and 4-wire<br />

connections<br />

• Parameterizable temperature coefficient with resistance-type<br />

sensors<br />

• Electrically isolated from load voltage supply 1L+ and 2L+<br />

• Linearization of sensor characteristics<br />

• Diagnostics "Open-circuit" per channel (terminals 1 and 3 are<br />

monitored for open-circuit)<br />

• Permissible common-mode voltage 10 Vpp AC<br />

Analog output modules<br />

EM 4 AO U High Feature<br />

• 4 outputs for voltage output<br />

• Output ranges:<br />

- ± 10 V, resolution 15 bit + sign<br />

- 1 to 5 V, resolution 14 bit<br />

- 0 to 10 V, resolution 15 bit<br />

• Electrically isolated from sensor supply voltage 1L+<br />

• Diagnostics "Short-circuit of sensor supply to M" per module<br />

• Diagnostics "Open-circuit in outputs" per channel<br />

• Substitute value output<br />

EM 4 AO I High Feature<br />

• 4 outputs for current output<br />

• Output ranges:<br />

- ± 20 mA, resolution 15 bit + sign<br />

- 4 to 20 mA, resolution 14 bit<br />

- 0 to 20 mA, resolution 15 bit<br />

• Electrically isolated from sensor supply voltage 1L+<br />

• Diagnostics "Short-circuit of sensor supply to M" per module<br />

• Diagnostics "Open-circuit" per channel<br />

• Substitute value output<br />

■ Technical specifications<br />

For detailed technical specifications of the analog electronics<br />

modules, see:<br />

• Catalog IK PI<br />

• Mall/CA 01 under "Distributed I/Os / ET 200pro"<br />

<strong>Siemens</strong> ST <strong>PCS</strong> 7 · November 2007<br />

11/61<br />