SIMATIC PCS 7 Process Control System - Siemens
SIMATIC PCS 7 Process Control System - Siemens
SIMATIC PCS 7 Process Control System - Siemens
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
11<br />
<strong>Process</strong> I/O<br />
ET 200S distributed I/O<br />
Power modules<br />
■ Overview<br />
PM-E power modules<br />
• For all types of electronic modules (including safety-oriented<br />
electronic modules); limitations resulting from power supply<br />
with PM-E DC 24 V<br />
• For monitoring and, depending on the version, fusing the voltage<br />
to electronic modules provided via the TM-P terminal<br />
module (load and sensor supply voltage)<br />
• Diagnostics message for voltage and blown fuse (can be<br />
switched off per configuration)<br />
• Two versions with different supply voltages:<br />
- PM-E DC 24 V (not for 2 DI AC 120 V, 2 DI AC 230 V and<br />
2 DO AC 24 to 230 V)<br />
- PM-E DC 24 to 48 V; AC 24 to 230 V; with additional fuse<br />
11/44<br />
<strong>Siemens</strong> ST <strong>PCS</strong> 7 · November 2007<br />
© <strong>Siemens</strong> AG 2007<br />
The TM-P terminal module of the power module interrupts the<br />
voltage buses (P1/P2) and therefore opens up a new potential<br />
group. All sensor and load supplies of the downstream electronics<br />
modules are fed from the TM-P and monitored by the power<br />
module. The total current of all modules of a potential group is<br />
limited by the maximum current carrying capacity of the power<br />
module (up to 10 A depending on the voltage and temperature<br />
range; for details, refer to the technical specifications of the<br />
power modules in Catalog IK PI).<br />
Possible combinations of the TM-P terminal modules and<br />
PM-E power modules<br />
TM-P terminal modules for power modules<br />
Screw-type 15S23-A1 15S23-A0 15S22-01 30S44-A0<br />
terminal<br />
6ES7 193-...<br />
...4CC20 -<br />
0AA0<br />
...4CD20 -<br />
0AA0<br />
...4CE00-<br />
0AA0<br />
...4CK20-<br />
0AA0<br />
Spring terminal TM- TM- TM- TM-<br />
6ES7 193-...<br />
P15C23-A1 P15C23-A0 P15C22-01 P30C44-A0<br />
...4CC30 - ...4CD30 - ...4CE10- ...4CK30-<br />
0AA0 0AA0 0AA0 0AA0<br />
Fast Connect TM- TM- TM- --<br />
6ES7 193-...<br />
P15N23-A1 P15N23-A0 P15N22-01<br />
...4CC70 - ...4CD70 - ...4CE60-<br />
Power modules<br />
0AA0 0AA0 0AA0<br />
PM-E DC 24 V • • •<br />
• • •<br />
PM-E<br />
DC 24 ... 48 V/<br />
AC 24 ... 230 V<br />
PM-E F DC 24 V<br />
PROFIsafe<br />
PM-D F DC 24 V<br />
PROFIsafe<br />
PM-E F power modules<br />
• For all non-safety-oriented types of electronic modules with ■ Selection and Ordering Data Order No.<br />
24 V DC supply<br />
Power module PM-E for electronics modules<br />
• For monitoring the voltage to electronic modules provided via<br />
the TM-P terminal module (load and sensor supply voltage)<br />
• For safe switching off of series-connected standard digital<br />
output modules 24 V DC (up to 10 A) via relay contacts (up to<br />
Cat. 3 according to EN 954 or SIL 2 according to IEC 61508):<br />
- 2 DO / 0.5 A standard, 6ES7 132-4BB01-0AA0<br />
- 2 DO / 2 A standard, 6ES7 132-4BB31-0AA0<br />
Power module PM-E<br />
• 24 V DC / 10 A<br />
- Monitoring of the load voltage<br />
• 24 ... 48 V DC; 24 ... 230 V AC<br />
- Monitoring of the fuse<br />
- Monitoring of the load voltage<br />
6ES7 138-4CA01-0AA0<br />
6ES7 138-4CB11-0AB0<br />
B)<br />
B)<br />
- 2 DO / 0.5 A high feature, 6ES7 132-4BB01-0AB0<br />
Power module PM-E F<br />
- 2 DO / 2 A high feature, 6ES7 132-4BB31-0AB0<br />
- 4 DO / 0.5 A standard, 6ES7 132-4BD01-0AA0<br />
- 4 DO / 2 A standard, 6ES7 132-4BD31-0AA0<br />
• PM-E F pm DC 24 V PROFIsafe<br />
- 1 x relay 24 V DC/10 A,<br />
P/M-switching, for switching-<br />
6ES7 138-4CF02-0AB0 B)<br />
• Two versions:<br />
- PM-E F pm DC 24 V PROFIsafe for ungrounded loads (separate<br />
ground and earth); with two additional safety-oriented<br />
digital outputs (p/m switching, up to Cat. 4 / SIL 3)<br />
- PM-E F pp DC 24 V PROFIsafe for grounded loads (ground<br />
off series-connected standard<br />
digital output modules (up to<br />
AK 4, SIL 2)<br />
- 2 x 24 V DC/2 A, P/M-switching,<br />
with wire breakage monitoring<br />
by channel<br />
and earth connected), e.g. actuators for connection to a<br />
(with "1" signal)<br />
central ground<br />
- Safe monitoring of communication<br />
with PROFIsafe<br />
■ Design<br />
- Diagnostics inside module<br />
- Overload diagnostics by chan-<br />
Depending on the possible combinations listed in the table, the<br />
power modules are plugged onto corresponding TM-P terminal<br />
modules. Power modules are suitable for dividing the ET 200S<br />
into potential groups. A power module must be provided at the<br />
beginning of each potential group. In addition, the first module<br />
following the IM 151-1 High Feature interface module must always<br />
be a power module.<br />
nel<br />
• PM-E F pp DC 24 V PROFIsafe<br />
- 1 x relay 24 V DC/10 A,<br />
P/P-switching, for switching-off<br />
series-connected standard<br />
digital output modules (up to<br />
AK 4, SIL 2)<br />
- Safe monitoring of communication<br />
with PROFIsafe<br />
- Diagnostics inside module<br />
- Overload diagnostics by channel<br />
6ES7 138-4CF41-0AB0 B)<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
•<br />
•