11<br />

<strong>Process</strong> I/O<br />

ET 200S distributed I/O<br />

Power modules<br />

■ Overview<br />

PM-E power modules<br />

• For all types of electronic modules (including safety-oriented<br />

electronic modules); limitations resulting from power supply<br />

with PM-E DC 24 V<br />

• For monitoring and, depending on the version, fusing the voltage<br />

to electronic modules provided via the TM-P terminal<br />

module (load and sensor supply voltage)<br />

• Diagnostics message for voltage and blown fuse (can be<br />

switched off per configuration)<br />

• Two versions with different supply voltages:<br />

- PM-E DC 24 V (not for 2 DI AC 120 V, 2 DI AC 230 V and<br />

2 DO AC 24 to 230 V)<br />

- PM-E DC 24 to 48 V; AC 24 to 230 V; with additional fuse<br />

11/44<br />

<strong>Siemens</strong> ST <strong>PCS</strong> 7 · November 2007<br />

© <strong>Siemens</strong> AG 2007<br />

The TM-P terminal module of the power module interrupts the<br />

voltage buses (P1/P2) and therefore opens up a new potential<br />

group. All sensor and load supplies of the downstream electronics<br />

modules are fed from the TM-P and monitored by the power<br />

module. The total current of all modules of a potential group is<br />

limited by the maximum current carrying capacity of the power<br />

module (up to 10 A depending on the voltage and temperature<br />

range; for details, refer to the technical specifications of the<br />

power modules in Catalog IK PI).<br />

Possible combinations of the TM-P terminal modules and<br />

PM-E power modules<br />

TM-P terminal modules for power modules<br />

Screw-type 15S23-A1 15S23-A0 15S22-01 30S44-A0<br />

terminal<br />

6ES7 193-...<br />

...4CC20 -<br />

0AA0<br />

...4CD20 -<br />

0AA0<br />

...4CE00-<br />

0AA0<br />

...4CK20-<br />

0AA0<br />

Spring terminal TM- TM- TM- TM-<br />

6ES7 193-...<br />

P15C23-A1 P15C23-A0 P15C22-01 P30C44-A0<br />

...4CC30 - ...4CD30 - ...4CE10- ...4CK30-<br />

0AA0 0AA0 0AA0 0AA0<br />

Fast Connect TM- TM- TM- --<br />

6ES7 193-...<br />

P15N23-A1 P15N23-A0 P15N22-01<br />

...4CC70 - ...4CD70 - ...4CE60-<br />

Power modules<br />

0AA0 0AA0 0AA0<br />

PM-E DC 24 V • • •<br />

• • •<br />

PM-E<br />

DC 24 ... 48 V/<br />

AC 24 ... 230 V<br />

PM-E F DC 24 V<br />

PROFIsafe<br />

PM-D F DC 24 V<br />

PROFIsafe<br />

PM-E F power modules<br />

• For all non-safety-oriented types of electronic modules with ■ Selection and Ordering Data Order No.<br />

24 V DC supply<br />

Power module PM-E for electronics modules<br />

• For monitoring the voltage to electronic modules provided via<br />

the TM-P terminal module (load and sensor supply voltage)<br />

• For safe switching off of series-connected standard digital<br />

output modules 24 V DC (up to 10 A) via relay contacts (up to<br />

Cat. 3 according to EN 954 or SIL 2 according to IEC 61508):<br />

- 2 DO / 0.5 A standard, 6ES7 132-4BB01-0AA0<br />

- 2 DO / 2 A standard, 6ES7 132-4BB31-0AA0<br />

Power module PM-E<br />

• 24 V DC / 10 A<br />

- Monitoring of the load voltage<br />

• 24 ... 48 V DC; 24 ... 230 V AC<br />

- Monitoring of the fuse<br />

- Monitoring of the load voltage<br />

6ES7 138-4CA01-0AA0<br />

6ES7 138-4CB11-0AB0<br />

B)<br />

B)<br />

- 2 DO / 0.5 A high feature, 6ES7 132-4BB01-0AB0<br />

Power module PM-E F<br />

- 2 DO / 2 A high feature, 6ES7 132-4BB31-0AB0<br />

- 4 DO / 0.5 A standard, 6ES7 132-4BD01-0AA0<br />

- 4 DO / 2 A standard, 6ES7 132-4BD31-0AA0<br />

• PM-E F pm DC 24 V PROFIsafe<br />

- 1 x relay 24 V DC/10 A,<br />

P/M-switching, for switching-<br />

6ES7 138-4CF02-0AB0 B)<br />

• Two versions:<br />

- PM-E F pm DC 24 V PROFIsafe for ungrounded loads (separate<br />

ground and earth); with two additional safety-oriented<br />

digital outputs (p/m switching, up to Cat. 4 / SIL 3)<br />

- PM-E F pp DC 24 V PROFIsafe for grounded loads (ground<br />

off series-connected standard<br />

digital output modules (up to<br />

AK 4, SIL 2)<br />

- 2 x 24 V DC/2 A, P/M-switching,<br />

with wire breakage monitoring<br />

by channel<br />

and earth connected), e.g. actuators for connection to a<br />

(with "1" signal)<br />

central ground<br />

- Safe monitoring of communication<br />

with PROFIsafe<br />

■ Design<br />

- Diagnostics inside module<br />

- Overload diagnostics by chan-<br />

Depending on the possible combinations listed in the table, the<br />

power modules are plugged onto corresponding TM-P terminal<br />

modules. Power modules are suitable for dividing the ET 200S<br />

into potential groups. A power module must be provided at the<br />

beginning of each potential group. In addition, the first module<br />

following the IM 151-1 High Feature interface module must always<br />

be a power module.<br />

nel<br />

• PM-E F pp DC 24 V PROFIsafe<br />

- 1 x relay 24 V DC/10 A,<br />

P/P-switching, for switching-off<br />

series-connected standard<br />

digital output modules (up to<br />

AK 4, SIL 2)<br />

- Safe monitoring of communication<br />

with PROFIsafe<br />

- Diagnostics inside module<br />

- Overload diagnostics by channel<br />

6ES7 138-4CF41-0AB0 B)<br />

B) Subject to export regulations: AL: N, ECCN: EAR99H<br />

•<br />