■ Overview<br />

The IM 153-2 High Feature interface module (electrical<br />

PROFIBUS DP transmission) or IM 153-2 FO High Feature interface<br />

module (optical PROFIBUS DP transmission) is required to<br />

connect the ET 200M remote I/O station to the PROFIBUS DP<br />

fieldbus. Depending on the fieldbus configuration (single/redundant),<br />

the ET 200M remote I/O station can be connected via one<br />

single or two redundant interface modules.<br />

The IM 153-2 High Feature supports the following functions:<br />

7 HART configuring of intelligent field devices<br />

7 Configuration of ET 200M I/Os in RUN mode of the automation<br />

system<br />

7 Connection to redundant AS 412H / AS 414H / AS 417H automation<br />

systems<br />

7 Use of ET 200M function modules (controller and counter<br />

modules)<br />

7 Operation of up to 12 I/O modules per remote I/O station<br />

7 Time stamping (SOE) with the safety-related SM 326F digital<br />

input module (F-DI24)<br />

7 Transmission of additional values with HART secondary variables<br />

of the HART SM 331 and SM 332 analog modules (up to<br />

4 per channel or up to 8 per module)<br />

On the other hand, the fiber-optic (FO) version IM 153-2 FO High<br />

Feature provides the following functions:<br />

7 HART configuring of intelligent field devices<br />

7 Configuration of ET 200M I/Os in RUN mode of the automation<br />

system<br />

7 Connection to redundant AS 412H, AS 414H and AS 417H<br />

automation systems<br />

7 Use of ET 200M function modules (controller and counter<br />

modules)<br />

7 Operation of up to 8 I/O modules per remote I/O station<br />

Notes:<br />

In order to use the hot swapping function, it is necessary to use the active<br />

bus modules and the DIN rail for hot swapping (refer to page 11/12).<br />

When using the IM 153-2 FO, additional plastic FOCs and an assembly<br />

set for Simplex connectors are required (refer to page 9/40).<br />

© <strong>Siemens</strong> AG 2007<br />

<strong>Process</strong> I/O<br />

ET 200M distributed I/O<br />

B) Subject to export regulations: AL: N, ECCN: EAR99H<br />

<strong>Siemens</strong> ST <strong>PCS</strong> 7 · November 2007<br />

Interface modules<br />

■ Selection and Ordering Data Order No.<br />

IM 153-2 High Feature<br />

Slave interface module for connection<br />

of an ET 200M to<br />

PROFIBUS DP, with time stamp<br />

(accuracy 1 ms), support of<br />

HART functionality, F modules,<br />

FM modules, "Configuration in<br />

RUN" function; also for use in<br />

redundant systems<br />

6ES7 153-2BA02-0XB0 B)<br />

IM 153-2 FO High Feature<br />

Slave interface module for connection<br />

of an ET 200M to optical<br />

PROFIBUS DP; support of HART<br />

functionality, F modules, FM modules,<br />

"Configuration in RUN" function;<br />

also for use in redundant<br />

systems<br />

6ES7 153-2BB00-0XB0 B)<br />

11/11<br />