SIMATIC PCS 7 Process Control System - Siemens
SIMATIC PCS 7 Process Control System - Siemens
SIMATIC PCS 7 Process Control System - Siemens
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
■ Overview<br />
The IM 153-2 High Feature interface module (electrical<br />
PROFIBUS DP transmission) or IM 153-2 FO High Feature interface<br />
module (optical PROFIBUS DP transmission) is required to<br />
connect the ET 200M remote I/O station to the PROFIBUS DP<br />
fieldbus. Depending on the fieldbus configuration (single/redundant),<br />
the ET 200M remote I/O station can be connected via one<br />
single or two redundant interface modules.<br />
The IM 153-2 High Feature supports the following functions:<br />
7 HART configuring of intelligent field devices<br />
7 Configuration of ET 200M I/Os in RUN mode of the automation<br />
system<br />
7 Connection to redundant AS 412H / AS 414H / AS 417H automation<br />
systems<br />
7 Use of ET 200M function modules (controller and counter<br />
modules)<br />
7 Operation of up to 12 I/O modules per remote I/O station<br />
7 Time stamping (SOE) with the safety-related SM 326F digital<br />
input module (F-DI24)<br />
7 Transmission of additional values with HART secondary variables<br />
of the HART SM 331 and SM 332 analog modules (up to<br />
4 per channel or up to 8 per module)<br />
On the other hand, the fiber-optic (FO) version IM 153-2 FO High<br />
Feature provides the following functions:<br />
7 HART configuring of intelligent field devices<br />
7 Configuration of ET 200M I/Os in RUN mode of the automation<br />
system<br />
7 Connection to redundant AS 412H, AS 414H and AS 417H<br />
automation systems<br />
7 Use of ET 200M function modules (controller and counter<br />
modules)<br />
7 Operation of up to 8 I/O modules per remote I/O station<br />
Notes:<br />
In order to use the hot swapping function, it is necessary to use the active<br />
bus modules and the DIN rail for hot swapping (refer to page 11/12).<br />
When using the IM 153-2 FO, additional plastic FOCs and an assembly<br />
set for Simplex connectors are required (refer to page 9/40).<br />
© <strong>Siemens</strong> AG 2007<br />
<strong>Process</strong> I/O<br />
ET 200M distributed I/O<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
<strong>Siemens</strong> ST <strong>PCS</strong> 7 · November 2007<br />
Interface modules<br />
■ Selection and Ordering Data Order No.<br />
IM 153-2 High Feature<br />
Slave interface module for connection<br />
of an ET 200M to<br />
PROFIBUS DP, with time stamp<br />
(accuracy 1 ms), support of<br />
HART functionality, F modules,<br />
FM modules, "Configuration in<br />
RUN" function; also for use in<br />
redundant systems<br />
6ES7 153-2BA02-0XB0 B)<br />
IM 153-2 FO High Feature<br />
Slave interface module for connection<br />
of an ET 200M to optical<br />
PROFIBUS DP; support of HART<br />
functionality, F modules, FM modules,<br />
"Configuration in RUN" function;<br />
also for use in redundant<br />
systems<br />
6ES7 153-2BB00-0XB0 B)<br />
11/11<br />
11