SIMATIC Industrial Software - Leocom
SIMATIC Industrial Software - Leocom
SIMATIC Industrial Software - Leocom
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
■ Technical specifications (continued)<br />
6ES7 671-<br />
0CC03-0YA0<br />
Timers/counters and their<br />
retentive characteristics<br />
(continued)<br />
IEC counter<br />
- available Yes Yes<br />
- Type SFB, unlimited<br />
quantity (only<br />
limited by working<br />
memory)<br />
6ES7 671-<br />
0RC04-0YA0<br />
SFB, unlimited<br />
quantity (only<br />
limited by working<br />
memory)<br />
S7 times<br />
-Number<br />
Retentivity<br />
512 512<br />
- lower limit 0 0<br />
- upper limit 511 511<br />
- preset<br />
Timing range<br />
0 0<br />
- lower limit 10 ms 10 ms<br />
- upper limit<br />
IEC timer<br />
9,990 s 9,990 s<br />
- available Yes Yes<br />
- Type SFB, unlimited<br />
quantity (only<br />
limited by working<br />
memory)<br />
Data areas and their retentive<br />
characteristics<br />
SFB, unlimited<br />
quantity (only<br />
limited by working<br />
memory)<br />
Retentivity without UPS and PS<br />
extension board<br />
No No<br />
Retentivity with UPS<br />
Flags<br />
all data all data<br />
-Number 2 KByte 2 KByte<br />
- of which retentive MB 0 - MB 2048 MB 0 - MB 2048<br />
- preset retentivity MB 0 - MB 15 MB 0 - MB 15<br />
- Number of clock memories<br />
Address area<br />
I/O address area<br />
8 8<br />
- Inputs 16 KByte 16 KByte<br />
-Outputs<br />
of which distributed<br />
16 KByte 16 KByte<br />
- DP interface, inputs 16 KByte 16 KByte<br />
- DP interface, outputs<br />
Process image<br />
16 KByte 16 KByte<br />
- Inputs, adjustable 8 KByte 8 KByte<br />
- Outputs, adjustable 8 KByte 8 KByte<br />
- Inputs, preset 512 Byte 512 Byte<br />
- Outputs, preset 512 Byte 512 Byte<br />
- Number of component<br />
process images, max.<br />
Digital channels<br />
15 15<br />
- Inputs 131,072 131,072<br />
-Outputs<br />
Analog channels<br />
131,072 131,072<br />
- Inputs 8,192 8,192<br />
-Outputs 8,192 8,192<br />
PC-based Automation<br />
PC-based Control<br />
<strong>SIMATIC</strong> WinAC <strong>Software</strong> PLC<br />
6ES7 671-<br />
0CC03-0YA0<br />
Configuration<br />
Number of DP masters<br />
- overall 4 4<br />
- via CP 4; CP 5611<br />
Integrated PB<br />
interface of the<br />
<strong>SIMATIC</strong> PC<br />
CP 5613<br />
CP 5613-A2<br />
Number of FMs and CPs that can<br />
be operated (recommendation)<br />
-FM FM distributed:<br />
FM350-1/350-2,<br />
FM 351,<br />
FM 352,<br />
FM 353,<br />
FM 354,<br />
FM 355,<br />
FM 355-2<br />
- CP, point-to-point CP 340, CP 341<br />
distributed<br />
Siemens ST 70 · 2005<br />
6ES7 671-<br />
0RC04-0YA0<br />
4; CP 5613<br />
CP 5613-A2<br />
FM distributed:<br />
FM 350-1/350-2,<br />
FM 351,<br />
FM 352,<br />
FM 353,<br />
FM 354,<br />
FM 355,<br />
FM 355-2<br />
CP 340, CP 341<br />
distributed<br />
- CP, LAN<br />
Time<br />
via PC-CP via PC-CP<br />
Clock<br />
- Hardware clock (realtime clock) Yes Yes<br />
- buffered<br />
Time synchronization<br />
Yes Yes<br />
- supported<br />
S7 message functions<br />
No No<br />
Number of stations that can log on<br />
for message functions, max.<br />
64 64<br />
SCAN method No No<br />
Process diagnostic messages Yes; Alarm_S Yes; Alarm_S<br />
Alarm 8 blocks No No<br />
Statuses<br />
Test and startup functions<br />
Status/modify<br />
No No<br />
- Variable<br />
Forcing<br />
Yes Yes<br />
- Forcing No No<br />
Status block Yes Yes<br />
Single step<br />
Diagnostic buffer<br />
Yes Yes<br />
- available Yes Yes<br />
- Number of inputs, max. 3,200 3,200<br />
- preset<br />
Communication functions<br />
120 120<br />
PG/OP communication<br />
Global data communication<br />
Yes Yes<br />
- supported<br />
S7 basic communication<br />
No No<br />
- supported<br />
S7 communication<br />
No No<br />
- as server Yes Yes<br />
- as client<br />
Number of connections<br />
Yes Yes<br />
- overall 64 64<br />
- reserved for PG communication 1 1<br />
- reserved for OP communication 1 1<br />
9/5<br />
9