13.07.2013 Views

SIMATIC Industrial Software - Leocom

SIMATIC Industrial Software - Leocom

SIMATIC Industrial Software - Leocom

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

6<br />

<strong>SIMATIC</strong> C7<br />

Control systems<br />

C7-636<br />

■ Technical specifications (continued)<br />

6ES7 636-2EC00-0AE3<br />

Operator control and monitoring<br />

Process pictures Yes<br />

Graphic objects Yes<br />

Text elements Yes<br />

Info texts Yes<br />

Messages Yes; Alarm messages,<br />

event messages<br />

Number of process pictures 300<br />

Number of variables per picture,<br />

max.<br />

200<br />

Number of variables in message<br />

text, max.<br />

8<br />

Password protection Yes<br />

Password levels<br />

Keyboard<br />

10<br />

- Type Membrane keyboard<br />

- Number of function keys 24; 18 with LED<br />

- Number of softkey keys<br />

Display<br />

14<br />

- Type CSTN, CCFL backlit,<br />

5,7" Color (256 colors)<br />

- Background lighting MTBF<br />

(at 20°C)<br />

Resolution (pixels)<br />

40,000 h<br />

- Width 320<br />

-Height<br />

Event/alarm messages<br />

240<br />

- Event messages Yes<br />

- Number of entries in process Message archive limited<br />

event buffer, max.<br />

by storage medium<br />

- Alarm messages Yes<br />

- Number of entries in the alarm Message archive limited<br />

message buffer, max.<br />

Recipes<br />

by storage medium<br />

- Number, max. 300<br />

- Data records per recipe, max. 500<br />

- Entries per data record, max.<br />

Insulation<br />

1,000<br />

Insulation tested with 500 V DC<br />

Potentials/ electrical isolation<br />

Analog output functions<br />

- Electrical isolation,<br />

Yes<br />

analog output functions<br />

- between the channels No<br />

- between the channels and Yes<br />

the backplane bus<br />

Analog output functions<br />

- Electrical isolation,<br />

Yes<br />

analog inputs<br />

- between the channels No<br />

- between the channels and the Yes<br />

backplane bus<br />

Digital output functions<br />

- Electrical isolation,<br />

Yes<br />

digital output functions<br />

- between the channels Yes<br />

- between the channels,<br />

8<br />

in groups of<br />

- between the channels and Yes<br />

the backplane bus<br />

6/28<br />

Siemens ST 70 · 2005<br />

6ES7 636-2EC00-0AE3<br />

Digital input functions<br />

- Electrical isolation,<br />

Yes<br />

digital input functions<br />

- between the channels No<br />

- between the channels and Yes<br />

the backplane bus<br />

Permissible potential difference<br />

between different circuits 75 V DC / 60 V AC<br />

Environmental requirements<br />

Environmental conditions<br />

Operating temperature<br />

Not suitable for open air use<br />

- 45 degree mounting, min. 0 °C<br />

- 45 degree mounting, max. 45 °C<br />

- vertical mounting, min. 0 °C<br />

- vertical mounting, max. 50 °C<br />

- horizontal mounting, min. 0 °C<br />

- horizontal mounting, max.<br />

Air pressure<br />

40 °C<br />

- Operation, min. 795 hPa<br />

- Operation, max. 1,080 hPa<br />

- Storage/transportation, min. 660 hPa<br />

- Storage/transportation, max. 1,080 hPa<br />

- permissible range, min 795 hPa<br />

- permissible range, max<br />

Relative humidity<br />

1,080 hPa<br />

- Operation, min. 5 %<br />

- Operation, max. 85 %; at