■ Technical specifications (continued)<br />

6ES7 673-<br />

2CC02-0YA0<br />

Timers/counters and their<br />

retentive characteristics<br />

(continued)<br />

IEC timer<br />

- available Yes Yes<br />

- Type SFB, unlimited<br />

quantity (only<br />

limited by working<br />

memory)<br />

S7 times<br />

-Number 256 512<br />

Retentivity<br />

- lower limit 0 0<br />

- upper limit 255 511<br />

- preset no timer is<br />

retentive<br />

6ES7 673-<br />

6CC22-0YA0<br />

SFB, unlimited<br />

quantity (only<br />

limited by working<br />

memory)<br />

no timer is<br />

retentive<br />

Timing range<br />

- lower limit 10 ms 10 ms<br />

- upper limit<br />

IEC timer<br />

9,990 s 9,990 s<br />

- available Yes Yes<br />

- Type SFB, unlimited SFB, unlimited<br />

quantity (only quantity (only<br />

limited by work- limited by work-<br />

Data areas and their<br />

retentive characteristics<br />

ing memory) ing memory)<br />

Retentivity without UPS and<br />

PS extension board<br />

No No<br />

Retentivity with UPS No No<br />

Retentivity with PS extension<br />

board and battery<br />

Flags<br />

all data all data<br />

-Number 4 KByte 16 KByte<br />

- of which retentive MB 0 to<br />

MB 4095<br />

MB 0 to<br />

MB 16383<br />

- preset retentivity MB 0 to MB 15 MB 0 to MB 15<br />

- Number of clock memories<br />

Address area<br />

I/O address area<br />

8 8<br />

- Inputs 4 KByte 16 KByte<br />

-Outputs<br />

of which distributed<br />

4 KByte 16 KByte<br />

- MPI/DP interface, inputs 2 KByte 2 KByte<br />

- MPI/DP interface, outputs 2 KByte 2 KByte<br />

- DP interface, inputs 4 KByte 8 KByte<br />

- DP interface, outputs<br />

Process image<br />

4 KByte 8 KByte<br />

- Inputs, adjustable 4 KByte 16 KByte<br />

- Outputs, adjustable 4 KByte 16 KByte<br />

- Inputs, preset 128 Byte 512 Byte<br />

- Outputs, preset 128 Byte 512 Byte<br />

- Number of component<br />

process images, max.<br />

Digital channels<br />

8 8<br />

- Inputs 32,768 81,920<br />

-Outputs<br />

Analog channels<br />

32,768 81,920<br />

- Inputs 2,048 5,120<br />

-Outputs 2,048 5,120<br />

PC-based Automation<br />

PC-based Control<br />

<strong>SIMATIC</strong> WinAC Slot PLC<br />

6ES7 673-<br />

2CC02-0YA0<br />

Configuration<br />

Number of DP masters<br />

- overall 2 2<br />

- integral 2 2<br />

Number of FMs and CPs that can<br />

be operated (recommendation)<br />

-FM FM distributed:<br />

FM 350-1,<br />

FM 350-2,<br />

FM 351,<br />

FM 352,<br />

FM 353,<br />

FM 354<br />

FM 355,<br />

FM 355-2<br />

Siemens ST 70 · 2005<br />

6ES7 673-<br />

6CC22-0YA0<br />

FM distributed:<br />

FM 350-1,<br />

FM 350-2,<br />

FM 351,<br />

FM 352,<br />

FM 353,<br />

FM 354,<br />

FM 355,<br />

FM 355-2<br />

- CP, LAN<br />

Time<br />

Clock<br />

via PC-CP via PC-CP<br />

- Hardware clock (realtime clock) Yes Yes<br />

- buffered<br />

Run-time meter<br />

Yes Yes<br />

- Quantity<br />

Time synchronization<br />

8 8<br />

- supported Yes Yes; (on PC-CP:<br />

Slave)<br />

- on PC-CP, slave Yes Yes<br />

- on MPI, master Yes Yes<br />

- on MPI, slave<br />

S7 message functions<br />

Yes Yes<br />

Number of stations that can log on<br />

for message functions, max.<br />

8 12<br />

SCAN method Yes Yes<br />

Process diagnostic messages Yes; (Alarm_S) Yes; (Alarm_S)<br />

Alarm 8 blocks Yes Yes<br />

Statuses<br />

Test and startup functions<br />

Yes Yes<br />

Status/modify<br />

- Variable<br />

Forcing<br />

Yes Yes<br />

- Forcing Yes Yes<br />

Status block Yes Yes<br />

Single step<br />

Diagnostic buffer<br />

Yes Yes<br />

- available Yes Yes<br />

- Number of inputs, max. 400 3,200<br />

- preset<br />

Communication functions<br />

120 120<br />

PG/OP communication<br />

Global data communication<br />

Yes Yes<br />

- supported<br />

S7 basic communication<br />

Yes Yes<br />

- supported<br />

S7 communication<br />

Yes Yes<br />

- as server Yes Yes<br />

- as client<br />

Number of connections<br />

Yes Yes<br />

- overall 16 64<br />

- reserved for PG communication 1 1<br />

- reserved for OP communication 1 1<br />