7<br />

<strong>SIMATIC</strong> <strong>Industrial</strong> <strong>Software</strong><br />

Runtime software<br />

Loadable drivers for CP 441-2 and CP 341<br />

■ Overview<br />

Driver for MODBUS protocol with RTU message format;<br />

communication as master or slave<br />

Driver for full-duplex protocol for Data Highway Asynchronous<br />

Link from Allen Bradley<br />

Loadable on CP 341 and CP 441-2 (6ES7 441-2AA03-0AE0)<br />

■ Technical specifications<br />

MODBUS master<br />

MODBUS protocol with RTU<br />

format<br />

Master/slave coupling:<br />

<strong>SIMATIC</strong> S7 is master<br />

Implemented function codes:<br />

01, 02, 03, 04, 05, 06, 07, 08,<br />

11,12,15,16<br />

No V.24 control and signaling<br />

lines<br />

CRC polynomial:<br />

X16 + x15 + x2 +1<br />

Interfaces: TTY (20 mA);<br />

V.24 (RS 232 C);<br />

X.27 (RS 422/485) two-wire or<br />

four-wire<br />

Inbox specified on BRCV<br />

Delay time 3.5 characters<br />

or multiple thereof<br />

Broadcast message possible<br />

Adjustable parameters Data transmission rate<br />

300 bit/s up to 76800 bit/s;<br />

(TTY to 19200 bit/s)<br />

Character frame<br />

With/without RS 485 mode<br />

for two-wire connections<br />

With/without modem mode<br />

(ignore scratch character)<br />

Response timer 100 ms to 25.5 s<br />

in steps of 100 ms<br />

Factor for character delay time<br />

1-10<br />

Default input of receive line<br />

when using X.27 interface<br />

module<br />

MODBUS slave<br />

MODBUS protocol with RTU<br />

format<br />

Master/slave coupling:<br />

<strong>SIMATIC</strong> S7 is slave<br />

Implemented function codes:<br />

01, 02, 03, 04, 05, 06, 08, 15, 16<br />

No V.24 control and signaling<br />

line<br />

CRC polynomial<br />

X16 + x15 + x2 + 1<br />

Interfaces: TTY (20 mA),<br />

V.24 (RS 232C),<br />

X.27 (RS 422/485) two-wire or<br />

four-wire<br />

Communication FB 180,<br />

instance DB 180 (use of a<br />

multi-instance)<br />

Conversion of MODBUS data<br />

address to S7 data areas.<br />

Processed data areas:<br />

DB, bit memories, outputs,<br />

inputs, timers, counters<br />

Delay time 3.5 characters<br />

or multiple thereof<br />

7/40<br />

Siemens ST 70 · 2005<br />

Configuring<br />

For loading and configuring the driver, the configuration<br />

package for CP 441-2 and CP 341, V4.0 upwards and<br />

STEP 7 V4.0 are necessary. The drivers are copy-protected<br />

by a dongle.<br />

MODBUS slave (continued)<br />

Adjustable parameters Data transmission rate<br />

300 bit/s up to 76800 bit/s;<br />

(TTY to 19200 bit/s)<br />

Character frame<br />

Slave address of CP (1 to 255)<br />

With/without RS 485 mode<br />

for two-wire connection<br />

With/without modem mode<br />

(ignore scratch character)<br />

Factor for character delay<br />

time 1-10<br />

Number of work DB<br />

(for FB processing)<br />

Enabling of memory areas for<br />

writing by master<br />

Default input of receive line<br />

when using X.27 interface<br />

module<br />

Conversion of MODBUS<br />

addresses to S7 data areas<br />

Data Highway<br />

Data highway full duplex (DF1)<br />

protocol<br />

Interfaces: TTY (20 mA), V.24<br />

(RS 232C), RS 422/485<br />

(four-wire)<br />

No “embedded responses”<br />

Adjustable parameters Data transmission rate 300 bit/s<br />

up to 76800 bit/s; (TTY to<br />

19200 bit/s)<br />

Character frame: 7/8 bit; 1/2<br />

stop bits; even/odd/no parity<br />

Inbox DB and data word<br />

Timeout for acknowledgment<br />

character: 30 ms to 10 s<br />

Number of repeats with NAK:<br />

0 to 5<br />

Number of ENQ prompts: 0 to 5<br />

Duplicate message transmission<br />

detection: On or Off<br />

Acknowledgment of CP immediately<br />

following receipt or only following<br />

transfer to CPU