9<br />

PC-based Automation<br />

PC-based Control<br />

<strong>SIMATIC</strong> WinAC <strong>Software</strong> PLC<br />

■ Technical specifications (continued)<br />

6ES7 671-<br />

0CC03-0YA0<br />

1st interface<br />

Type of interface CP 5611,<br />

<strong>SIMATIC</strong> PC<br />

integral<br />

Number of simultaneous operable 1<br />

CPs, max.<br />

Physical RS 485 /<br />

PROFIBUS<br />

Isolated Yes<br />

Functionality<br />

-MPI No<br />

-DP master Yes<br />

- DP slave No<br />

DP master<br />

- Number of connections, max. 8<br />

Services<br />

- PG/OP communication Yes<br />

- Routing Yes<br />

- Global data communication No<br />

- S7 basic communication No<br />

- S7 communication Yes<br />

- Equidistance support No<br />

- SYNC/FREEZE Yes<br />

- Activate/deactivate DP slaves Yes<br />

- Direct data exchange (lateral Yes<br />

communication)<br />

-DPV0 Yes<br />

-DPV1 No<br />

- Transmission rates, max. 12 Mbit/s<br />

- Number of DP slaves, max. 32<br />

Address area<br />

- Inputs, max. 16 KByte<br />

-Outputs, max. 16 KByte<br />

User data per DP Slave<br />

- Inputs, max. 244 Byte<br />

-Outputs, max. 244 Byte<br />

2nd interface<br />

Type of interface CP 5613,<br />

CP 5613-A2<br />

Number of simultaneous operable<br />

CPs, max.<br />

Physical RS 485 /<br />

PROFIBUS<br />

9/6<br />

Siemens ST 70 · 2005<br />

4 4<br />

Isolated<br />

Functionality<br />

Yes Yes<br />

-MPI No No<br />

-DP master Yes Yes<br />

- DP-Slave No No<br />

- PROFINET CBA No<br />

- PROFINET CBA-SRT No<br />

- PROFINET IO-Controller No<br />

6ES7 671-<br />

0RC04-0YA0<br />

CP 5613,<br />

CP 5613-A2<br />

RS 485 /<br />

PROFIBUS<br />

6ES7 671-<br />

0CC03-0YA0<br />

6ES7 671-<br />

0RC04-0YA0<br />

2nd interface (continued)<br />

DP master<br />

- Number of connections, max.<br />

Services<br />

50 50<br />

- PG/OP communication Yes Yes<br />

- Routing Yes Yes<br />

- Global data communication No No<br />

- S7 basic communication No No<br />

- S7 communication Yes Yes<br />

- Equidistance support Yes Yes<br />

- SYNC/FREEZE Yes Yes<br />

- Activate/deactivate DP slaves Yes Yes<br />

- Direct data exchange (lateral<br />

communication)<br />

Yes Yes<br />

-DPV0 Yes Yes<br />

-DPV1 Yes Yes<br />

- Transmission rates, max. 12 Mbit/s 12 Mbit/s<br />

- Number of DP slaves, max.<br />

Address area<br />

125 125<br />

- Inputs, max. 16 KByte 16 KByte<br />

- Outputs, max.<br />

User data per DP Slave<br />

16 KByte 16 KByte<br />

- Inputs, max. 244 Byte 244 Byte<br />

- Outputs, max.<br />

Clock synchronism<br />

244 Byte 244 Byte<br />

Clock synchronous operation No Yes<br />

Number of DP masters with clock<br />

synchronism<br />

2<br />

User data per clock synchronous<br />

slave, max.<br />

128 Byte<br />

Equidistance<br />

Yes<br />

Shortest clock pulse<br />

CPU/ programming<br />

2.2 ms; 2.2 ms<br />

without process<br />

image<br />

section; 2.2 ms<br />

with process<br />

image section<br />

Programming language<br />

- STEP 7 Yes; as of V5.2,<br />

engineering<br />

tools (optional)<br />

-LAD Yes Yes<br />

-FBD Yes Yes<br />

-STL Yes Yes<br />

-SCL Yes Yes<br />

-CFC Yes Yes<br />

- GRAPH Yes Yes<br />

- HiGraph ® <strong>Software</strong> library<br />

Yes Yes<br />

- Easy Motion Control Yes Yes<br />

Bracket levels 8 8<br />

User program protection/<br />

password protection<br />

No No<br />

Yes; as of V5.2,<br />

engineering<br />

tools (optional)