Block Transfer Failure at Startup<br />

Block Transfer Failure at Startup<br />

4<br />

RIO Block Transfer 7-117<br />

M0 Control Information<br />

M1 Status Information<br />

In the above example, the scanner found invalid control information<br />

(e.g., an improper logical address) in the M0 block transfer control<br />

buffer.<br />

1. The SLC control program fills in the M0 BT buffer and sets the<br />

EN flag.<br />

2. The scanner detects that the EN flag is set, determines that there<br />

is some invalid information in the M0 control buffer, fills in the<br />

M1 BT buffer status error code field, and sets the ER flag.<br />

3. The SLC control program detects the ER flag, examines the M1<br />

BT status buffer error code, and clears the EN flag after<br />

processing the error.<br />

4. The scanner detects that the SLC control program has processed<br />

the error and clears the ER flag.<br />

Note that in this example the EW and ST flags never set. Also, the<br />

SLC control program must clear the EN flag in order to start a new<br />

BT after the error has been corrected.<br />