1747-6.22, Backup Scanner User Manual
1747-6.22, Backup Scanner User Manual
1747-6.22, Backup Scanner User Manual
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
0021<br />
0022<br />
0023<br />
0024<br />
0025<br />
0026<br />
0027<br />
0028<br />
Programming Techniques 9-175<br />
This rung monitors the DTCW and DTSW bits for Data Block #11. When a transfer of data using Data Block #11 is not in progress, copy up to 128 words to the appropriate<br />
M-file location for Data Block #11 in the BSN module.<br />
B3:5 B3:6<br />
COP<br />
Copy File<br />
10 10<br />
Source #N18:0<br />
Dest #M0:1.4780<br />
Length 128<br />
Unlatch the virtual DTCW bit for Data Block #11 when the comparable virtual DTSW bit is set by the BSN module to indicate that it has received the last data via data Block<br />
#11. when B3:7/10 has been unlatched, the BSN module is ready for the next data transfer via Data Block #11.<br />
B3:6<br />
B3:7<br />
U<br />
10<br />
10<br />
This rung monitors the DTCW and DTSW bits for Data Block #12. When a transfer of data using Data Block #12 is not in progress, copy up to 128 words to the appropriate<br />
M-file location for Data Block #12 in the BSN module.<br />
B3:5 B3:6<br />
COP<br />
Copy File<br />
11 11<br />
Source #N18:128<br />
Dest #M0:1.4908<br />
Length 128<br />
Unlatch the virtual DTCW bit for Data Block #12 when the comparable virtual DTSW bit is set by the BSN module to indicate that it has received the last data via data Block<br />
#12. when B3:7/11 has been unlatched, the BSN module is ready for the next data transfer via Data Block #12.<br />
B3:6<br />
B3:7<br />
U<br />
11<br />
11<br />
This rung monitors the DTCW and DTSW bits for Data Block #13. When a transfer of data using Data Block #13 is not in progress, copy up to 128 words to the appropriate<br />
M-file location for Data Block #13 in the BSN module.<br />
B3:5 B3:6<br />
COP<br />
Copy File<br />
12 12<br />
Source #N19:0<br />
Dest #M0:1.5036<br />
Length 128<br />
Unlatch the virtual DTCW bit for Data Block #13 when the comparable virtual DTSW bit is set by the BSN module to indicate that it has received the last data via data Block<br />
#13. when B3:7/12 has been unlatched, the BSN module is ready for the next data transfer via Data Block #13.<br />
B3:6<br />
B3:7<br />
U<br />
12<br />
12<br />
This rung monitors the DTCW and DTSW bits for Data Block #14. When a transfer of data using Data Block #14 is not in progress, copy up to 128 words to the appropriate<br />
M-file location for Data Block #14 in the BSN module.<br />
B3:5 B3:6<br />
COP<br />
Copy File<br />
13 13<br />
Source #N19:128<br />
Dest #M0:1.5164<br />
Length 128<br />
Unlatch the virtual DTCW bit for Data Block #14 when the comparable virtual DTSW bit is set by the BSN module to indicate that it has received the last data via data Block<br />
#14. when B3:7/13 has been unlatched, the BSN module is ready for the next data transfer via Data Block #14.<br />
B3:6<br />
B3:7<br />
U<br />
13<br />
13<br />
B3:7<br />
L<br />
10<br />
B3:7<br />
L<br />
11<br />
B3:7<br />
L<br />
12<br />
B3:7<br />
L<br />
13<br />
Publication <strong>1747</strong>-<strong>6.22</strong>