9-170 Programming Techniques<br />

0013<br />

0014<br />

0015<br />

0016<br />

This rung copies the "new" Data Block #13 data from the secondary BSN to a file within the secondary processor. When the COPy is complete, the DTHW (Data Table<br />

handshake Word) bit for Data Block #13 (B3:4/12 = M0:1.3411/12) must be set to inform the secondary BSN that the secondary processor has received the latest Data Block<br />

and is now ready for the next block of data via Data Block #13.<br />

Virtual DTSW Bit for<br />

Data Block #13<br />

B3:3<br />

12<br />

Publication <strong>1747</strong>-<strong>6.22</strong><br />

COP<br />

Copy File<br />

Source #M1:1.5036<br />

Dest #N18:0<br />

Length 128<br />

Virtual DTHW Bit for<br />

Data Block #13<br />

B3:4<br />

This rung copies the "new" Data Block #14 data from the secondary BSN to a file within the secondary processor. When the COPy is complete, the DTHW (Data Table<br />

handshake Word) bit for Data Block #14 (B3:4/13 = M0:1.3411/13) must be set to inform the secondary BSN that the secondary processor has received the latest Data Block<br />

and is now ready for the next block of data via Data Block #14.<br />

Virtual DTSW Bit for<br />

Data Block #14<br />

B3:3<br />

13<br />

COP<br />

12<br />

Copy File<br />

Source #M1:1.5164<br />

Dest #N18:128<br />

Length 128<br />

Virtual DTHW Bit for<br />

Data Block #14<br />

B3:4<br />

This rung copies the "new" Data Block #15 data from the secondary BSN to a file within the secondary processor. When the COPy is complete, the DTHW (Data Table<br />

handshake Word) bit for Data Block #15 (B3:4/14 = M0:1.3411/14) must be set to inform the secondary BSN that the secondary processor has received the latest Data Block<br />

and is now ready for the next block of data via Data Block #15.<br />

Virtual DTSW Bit for<br />

Data Block #15<br />

B3:3<br />

14<br />

COP<br />

13<br />

Copy File<br />

Source #M1:1.5292<br />

Dest #N19:0<br />

Length 128<br />

Virtual DTHW Bit for<br />

Data Block #15<br />

B3:4<br />

This rung copies the "new" Data Block #16 data from the secondary BSN to a file within the secondary processor. When the COPy is complete, the DTHW (Data Table<br />

handshake Word) bit for Data Block #16 (B3:4/15 = M0:1.3411/15) must be set to inform the secondary BSN that the secondary processor has received the latest Data Block<br />

and is now ready for the next block of data via Data Block #16.<br />

Virtual DTSW Bit for<br />

Data Block #16<br />

B3:3<br />

15<br />

COP<br />

14<br />

Copy File<br />

Source #M1:1.5420<br />

Dest #N19:128<br />

Length 128<br />

Virtual DTHW Bit for<br />

Data Block #16<br />

B3:4<br />

15