B-202 M0-M1 Files and G Files<br />

Publication <strong>1747</strong>-<strong>6.22</strong><br />

COP<br />

COPY FILE<br />

Source #B3:0<br />

Dest #M0:1.0<br />

Length 34<br />

If you are using a SLC 5/02 Series B processor, add 1580 µs plus 670<br />

µs per word of data addressed to the M0 or M1 file. As shown above,<br />

34 words are copied from #B3:0 to M0:1.0. Therefore, this adds<br />

24360 µs to the scan time of the COP instruction. If you are using a<br />

SLC 5/02 Series C processor, add 950 µs plus 400 µs per word. This<br />

adds 14550 µs to the scan time of the COP instruction.<br />

SLC 5/03 Processor Example<br />

COP<br />

COPY FILE<br />

Source #B3:0<br />

Dest #M0:1.0<br />

Length 34<br />

The SLC 5/03 processor access times depend on the instruction type.<br />

Consult the table on B-5 for the correct access times to add. As an<br />

example, if you use a COP to M file instruction like the one shown<br />

above, add 772 µs plus 23 µs per word. This adds 1554 µs to the SLC<br />

5/03 processor scan time due to the COP instruction.<br />

SLC 5/04 Processor Example<br />

COP<br />

COPY FILE<br />

Source #B3:0<br />

Dest #M0:1.0<br />

Length 34<br />

The SLC 5/04 processor access times depend on the instruction type.<br />

Consult the table on B-5 for the correct access times to add. As an<br />

example, if you use a COP to M file instruction like the one shown<br />

above, add 735 µs plus 23 µs per word. This adds 1517 µs to the SLC<br />

5/04 processor scan time due to the COP instruction.<br />

Minimizing the Scan Time<br />

You can keep the processor scan time to a minimum by economizing<br />

on the use of instructions addressing the M0 or M1 files. For<br />

example, XIC instruction M0:2.1/1 is used in rungs 1 and 2 of the<br />

figure below, adding approximately 2 ms to the scan time if you are<br />

using a SLC 5/02 Series B processor.