Access Time<br />

M0-M1 Files and G Files B-201<br />

During the program scan, the processor must access the specialty I/O<br />

card to read/write M0 or M1 data. This access time must be added to<br />

the execution time of each instruction referencing M0 or M1 data.<br />

For the SLC 5/03 and SLC 5/04 processors, the instruction types vary<br />

in their execution times.<br />

The following table shows approximate access times per instruction<br />

or word of data for the SLC 5/02, SLC 5/03, and SLC 5/04<br />

processors.<br />

Processor Instruction Type<br />

Access Time per Bit<br />

Instruction or Word<br />

of Data<br />

Access Time per<br />

Multi-Word Instruction<br />

SLC 5/02 Series B All types 1<br />

1930 µs 1580 µs plus 670 µs per word<br />

SLC 5/02 Series C All types 1<br />

1160 µs 950 µs plus 400 µs per word<br />

SLC 5/03 (All<br />

Series)<br />

XIC or XIO 782 µs --<br />

OTU, OTE, or OTL 925 µs --<br />

COP to M file -- 772 µs plus 23 µs per word<br />

COP from M file -- 760 µs plus 22 µs per word<br />

FLL -- 753 µs plus 30 µs per word<br />

MVM to M file 894 µs -any<br />

source or Destination M<br />

file address<br />

730 µs --<br />

SLC 5/04 OS400 XIC or XIO 743 µs --<br />

OTU, OTE, or OTL 879 µs --<br />

COP to M file -- 735 µs plus 23 µs per word<br />

COP from M file -- 722 µs plus 22 µs per word<br />

FLL -- 716 µs plus 30 µs per word<br />

MVM to M file 850 µs -any<br />

source or Destination M<br />

file address<br />

694 µs --<br />

1. Except the OSR instruction and the instruction parameters noted on page C-2.<br />

SLC 5/02 Processor Example<br />

M0:2.1<br />

] [<br />

1<br />

M1:3.1<br />

]/[<br />

1<br />

( )<br />

M0:2.1<br />

10<br />

If you are using a SLC 5/02 Series B processor, add 1930 µs to the<br />

program scan time for each bit instruction addressed to an M0 or M1<br />

data file. If you are using a SLC 5/03 Series C processor, add 1160<br />

µs.<br />

Publication <strong>1747</strong>-<strong>6.22</strong>