1747-6.22, Backup Scanner User Manual
1747-6.22, Backup Scanner User Manual
1747-6.22, Backup Scanner User Manual
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Switchover Considerations 8-161<br />
During this time, while the stations reconstruct the link,<br />
communication is interrupted. The length of the interruption depends<br />
on the number of stations involved in the link and the number of<br />
messages received and/or transmitted. This time is typically less than<br />
50 ms per station.<br />
However, while the link is rebuilding, messages can collide,<br />
increasing the amount of time needed to reconstruct the link. As a<br />
result, on a typical DH+ link with 6 - 10 stations, the impact on the<br />
link due to switchover could be the loss of communication for as<br />
much as 1 - 3 seconds.<br />
DH+ switching occurs whenever there is a transfer of control from<br />
the primary to the secondary processor. The switchover could result<br />
from a power failure or because of other system failures. The table<br />
below shows what can happen to the link if the token is lost.<br />
Important: Note that when a transfer of control from the primary to<br />
the secondary processor occurs, the processor that is<br />
now primary has the node address of n on the DH+ link.<br />
The processor that is now secondary has the node<br />
address of n +1.<br />
If the new primary is: the following could occur causing this result<br />
Polling the link<br />
Listening to the link<br />
Message packet from another<br />
station disrupted<br />
Reply packet disrupted Same as above<br />
Token pass packet disrupted<br />
New primary processor takes<br />
the token<br />
New primary processor receives<br />
a message from another station<br />
The source station turns on error bit in its MSG instruction You<br />
provide programming at the source station to regain<br />
synchronization with the receiving station. You can do this by<br />
monitoring the message instruction error bit as a condition for<br />
retransmitting the message.<br />
The DH+ link times out and must rebuild. (250ms watchdog timeout)<br />
+ (50 ms x number of stations on the link).<br />
The new primary processor has nothing in its active node table. The<br />
DH+ link times out and must rebuild. (250 ms watchdog timeout) +<br />
(50 ms x number of stations on the link).<br />
The link continues working normally.<br />
Important: In the recommended configuration, set both SLC 500<br />
processors to the same station address. The backup<br />
modules permit only one of the two processors to be<br />
connected to the DH+ at a time. In this configuration,<br />
remote PLC processors and operator stations<br />
communicate to the processor that currently has primary<br />
status. Note that the secondary processor can also be<br />
accessed through the primary SLC 500 processor node<br />
address plus one (n+1).<br />
Publication <strong>1747</strong>-<strong>6.22</strong>