4<br />

20 4 5<br />

VALVE ISLANDS - GENERATION C<br />

DEVICE NET<br />

COMMUNICATION CHARACTERISTICS<br />

Communication protocol DEVICE NET (Allen Bradley)<br />

Transmission shielded 2x2-wire cable, twisted in pairs (2 power supply, 2 signal wires)<br />

Bus structure line or tree structure<br />

Max. number of valve islands 63<br />

Max. bus cable length 500 m at a transmission speed of 125 kbaud<br />

200 m at a transmission speed of 250 kbaud<br />

100 m at a transmission speed of 500 kbaud<br />

Transmission speed 125, 250 or 500 kbaud, adjustable with integrated DIP switches<br />

Island addressing (participants) 8 DIP switches integrated in the connector housing<br />

Compatibility with control system no modifi cation of current programs<br />

ELECTRICAL CHARACTERISTICS<br />

24 V supply connection 4-pin male M18 connector<br />

Bus connection (IN/OUT) 5-pin male 7/8" UN connector<br />

FIPIO<br />

COMMUNICATION CHARACTERISTICS<br />

Communication protocol FIPIO / World FIP<br />

Transmission shielded twisted pair<br />

Bus structure line or tree structure with repeaters<br />

wiring with TSX FP ACC4 junction boxes or T-connectors<br />

Max. number of valve islands 62 islands, 32 per segment with ACC4 connectors, 24 per segment with T-connectors<br />

Max. bus cable length 1000 m per segment<br />

max. 5000 m<br />

Transmission speed 1 MBaud<br />

Island addressing 8 DIP switches integrated in the connector housing<br />

ELECTRICAL CHARACTERISTICS<br />

24 V supply connection 4-pin male M18 connector<br />

Bus connection (IN/OUT) 5-pin male M12 connector<br />

MODBUS<br />

COMMUNICATION CHARACTERISTICS<br />

Communication protocol Modbus in RTU format, 8 bits with parity<br />

Transmission shielded 2-wire cable, twisted in pairs, conforming to RS 485 interface<br />

Bus structure line structure<br />

Max. number of valve islands 255<br />

Max. bus cable length 1200 m<br />

Transmission speed 4800, 9600 or 19200 baud, adjustable with integrated DIP switches<br />

Island addressing (participants) 8 DIP switches integrated in the connector housing<br />

Compatibility with control system no modifi cation of current programs<br />

ELECTRICAL CHARACTERISTICS<br />

24 V supply connection 4-pin male M18 connector<br />

Bus connection (IN/OUT) 5-pin male M12 connector<br />

VALVE ISLAND DESCRIPTION<br />

18<br />

Spool valve<br />

series<br />

Ports<br />

1 - 3 - 5<br />

569 G1/8<br />

570 G1/4<br />

571 G3/8<br />

All leafl ets are available on: www.asconumatics.eu<br />

6<br />

MULTIPOL WITHOUT INPUTS<br />

5<br />

1<br />

3<br />

21<br />

8<br />

1<br />

5<br />

1<br />

3<br />

00455GB-2007/R01<br />

Availability, design and specifi cations are subject to change without notice. All rights reserved.