Predictive Control of Three Phase AC/DC Converters
Predictive Control of Three Phase AC/DC Converters
Predictive Control of Three Phase AC/DC Converters
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
88 CHAPTER 5. INVESTIGATIONS OF CONTROL METHODS PERFORMANCE<br />
u La<br />
u Lb<br />
u Lc<br />
(a)<br />
VF-CSF-P-DPC<br />
i La<br />
(b)<br />
u La<br />
U <strong>DC</strong><br />
i La<br />
P ref<br />
Figure 5.18: Operation under two phase voltage sag: (a) line voltages u La , u Lb ,<br />
u Lc (100 V/div), line current i La (10 A/div), (b) line voltage u La (200 V/div),<br />
U <strong>DC</strong> voltage (100 V/div), line current i La (10 A/div), referenced active power<br />
P ref (1 kW/div)<br />
(see Fig. 4.11), which increases line current value. For both controls, the operational<br />
limit is set to the maximum allowable converter input current. When<br />
the current limit is exceeded, the converter is being shut down. The converter<br />
operates in similar way in case <strong>of</strong> two phase voltage sag.<br />
Figure 5.17 shows line current T HD factor in presence <strong>of</strong> single and two phase<br />
voltage sags. In both cases, the VF-CSF-P-DPC is more robust to disturbances,<br />
than control with direct line voltage measurements.