plc analog - 22.25<br />

5.<br />

A card with a voltage range from -10V to +10V will be selected to cover the<br />

entire range.<br />

R = ---------------------------------<br />

10V – (–<br />

10V)<br />

= 400 minimum resolution<br />

0.050V<br />

8 bits = 256<br />

9 bits = 512<br />

10 bits = 1024<br />

The A/D converter needs a minimum of 9 bits, but this number of bits is not<br />

commonly available, but 10 bits is, so that will be selected.<br />

V<br />

V max<br />

– V min<br />

ERROR<br />

= ⎛----------------------------<br />

⎞ =<br />

10V – (–<br />

10V)<br />

⎝ 2R ⎠<br />

--------------------------------- = ±<br />

2( 1024)<br />

0.00976V<br />