plc function ref - 34.40<br />

ARD, ARL - Ascii ReaD, Ascii Read Line<br />

Description:<br />

A<br />

ARD<br />

ASCII READ<br />

Channel<br />

Dest<br />

<strong>Control</strong><br />

String Length<br />

Characters Read<br />

0<br />

ST10:0<br />

R6:10<br />

15<br />

The ARD instruction will read characters <strong>and</strong> write them to a string. In<br />

this example the characters are read from channel 0 <strong>and</strong> written to<br />

’ST10:0’. All of the characters in the buffer, up to 15 in total, will be<br />

removed <strong>and</strong> written to the string memory. The number of characters<br />

will be stored in ’R6:10.POS’.<br />

The ARL function is similar to the ARD function, except that the end-ofline<br />

values ’CR’ or ’LF’ will mark the end of a line. With the parameters<br />

above the string will be copied until 15 characters are reached, or<br />

there are fewer than 15 characters, or an end-of-line character is<br />

found.<br />

Status Bits:<br />

EN<br />

DN<br />

ER<br />

UL<br />

EM<br />

EU<br />

enable - will be set while the instruction is enabled<br />

done - will be set when then string has been read<br />

error - will be set if an error has occurred<br />

unload -<br />

empty - will be set if no characters were found<br />

queue -<br />

Registers: POS the number of characters copied<br />

Available on: Micrologix, PLC-5<br />

www.PA<strong>Control</strong>.com