plc function ref - 34.10<br />

RTO - RetentiveTimer On<br />

A<br />

Description:<br />

Status Bits:<br />

Registers:<br />

RTO<br />

RETENTIVE TIMER ON<br />

Timer T4:0<br />

Time Base 1.0<br />

Preset 10<br />

Accum. 0<br />

This timer will delay turning on. When the input turns on the accumulated<br />

value (ACC) will start to increase from zero. When the preset (PRE)<br />

value is reached the DN bit is set. If the input goes false the accumulator<br />

value is not reset to zero. To reset the timer <strong>and</strong> turn off the timer the<br />

RES instruction should be used.<br />

EN<br />

TT<br />

DN<br />

ACC<br />

PRE<br />

Available on: Micrologix, PLC-5<br />

This bit is true while the input to the timer is true<br />

This bit is true while the accumulator value is increasing<br />

This bit is true when the accumulator value is less than the preset<br />

value<br />

The time that has passed since the input went true<br />

The maximum time delay before the timer goes on<br />

34.1.4 Compare<br />

CMP - CoMPare<br />

CMP<br />

COMPARE<br />

Expression<br />

“(N7:0 + 8) > N7:1”<br />

A<br />

Description:<br />

Status Bits:<br />

This function uses a free form expression to compare the two values. The<br />

comparison values that are allowed include =, >, >=, ,