plc electrical - 31.12<br />

When designing <strong>and</strong> building electrical control systems, the following points<br />

should prove useful.<br />

• Avoid ground loops<br />

- Connect the enclosure to the ground bus.<br />

- Each PLC component should be grounded back to the main PLC chassis.<br />

The PLC chassis should be grounded to the backplate.<br />

- The ground wire should be separated from power wiring inside enclosures.<br />

- Connect the machine ground to the enclosure ground.<br />

• Ensure good electrical connection<br />

- Use star washers to ensure good electrical connection.<br />

- Mount ground wires on bare metal, remove paint if needed.<br />

- Use 12AWG str<strong>and</strong>ed copper for PLC equipment grounds <strong>and</strong> 8AWG<br />

str<strong>and</strong>ed copper for enclosure backplate grounds.<br />

- The ground connection should have little resistance (