Table 7.1 Summary <strong>of</strong> Experiments for Each Group <strong>of</strong> Tests.<br />

Import<br />

<strong>Power</strong> From<br />

the Grid<br />

Export<br />

<strong>Power</strong> From<br />

the Grid<br />

Unit 1 Unit 2 (*) NOT there if both unit control unit output power, P<br />

50% 50% Isl<strong>and</strong>ing<br />

10% 90% Wrong Setpoint at One <strong>of</strong> the Units <strong>Control</strong>ling F (*)<br />

10% 90% Isl<strong>and</strong>ing, to Operating Point (i)<br />

10% 90% From Isl<strong>and</strong>, (i), Remove a Load<br />

10% 90% From Isl<strong>and</strong>, (i), Reduce Setpoint <strong>of</strong> Unit at Maximum <strong>Power</strong><br />

90% 10% Wrong Setpoint at One <strong>of</strong> the Units <strong>Control</strong>ling F (*)<br />

90% 10% Isl<strong>and</strong>ing<br />

50% 50% Isl<strong>and</strong>ing<br />

10% 90% Isl<strong>and</strong>ing<br />

90% 10% Isl<strong>and</strong>ing, to Operating Point (e)<br />

90% 10% From Isl<strong>and</strong>, (e), Insert a Load<br />

90% 10% From Isl<strong>and</strong>, (e), Increase Setpoint <strong>of</strong> Unit at Zero <strong>Power</strong><br />

7.1 Choice <strong>of</strong> Setpoints for the Series Configuration<br />

There are four possible control choices in the series configuration:<br />

i) unit 1 controlling P, unit 2 controlling P<br />

ii) unit 1 controlling F, unit 2 controlling F<br />

iii) unit 1 controlling F, unit 2 controlling P<br />

iv) unit 1 controlling P, unit 2 controlling F<br />

For each choice (see Table 7.1), there is an experiment when unit 1 is at 10% <strong>of</strong> its output power,<br />

while unit 2 is at 90% <strong>of</strong> its output power <strong>and</strong> the system transfers to isl<strong>and</strong>. Figure 7.2 shows the<br />

series configuration with all the loads, highlighting the fact that the only event taking place is the<br />

transition to isl<strong>and</strong>. The system is importing from the grid.<br />