02.06.2014 Views

Control and Design of Microgrid Components - Power Systems ...

Control and Design of Microgrid Components - Power Systems ...

Control and Design of Microgrid Components - Power Systems ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

cable <strong>of</strong> the 4 wire system inside the microgrid. Due to the connectivity <strong>of</strong> the transformer<br />

secondary, any kind <strong>of</strong> load can be connected on the feeders <strong>of</strong> the microgrid: three phase loads<br />

connected at delta or wye <strong>and</strong> single phase loads between a live phase <strong>and</strong> the neutral such as<br />

commercial appliances.<br />

The transformer provides electrical insulation between the voltages on the feeder <strong>and</strong> the<br />

voltages <strong>of</strong> the inverter side through the magnetic coupling <strong>of</strong> the coils. The choice <strong>of</strong> the delta to<br />

star connectivity provides also a filter for the zero sequence currents that may flow in the feeder<br />

due to a fault: this provides the power electronic devices <strong>of</strong> the inverter with a level <strong>of</strong> protection<br />

from faults.<br />

(a)<br />

(b)<br />

Figure 4.12 Transformer Current During Fault on a) Wye Side, b) Delta Side.<br />

Figure 4.12 shows the line currents flowing on the wye <strong>and</strong> delta side as a consequence <strong>of</strong> a<br />

single line to ground fault on the feeder side without the intervention <strong>of</strong> protections to open the<br />

circuit. For ease <strong>of</strong> comparison, the transformer has a unitary turn ratio resulting in same line<br />

current magnitudes on either side. Normal loading conditions determine a current <strong>of</strong> about 50A,<br />

but as soon as the fault is applied the currents on the wye side reach over 400A in the faulted<br />

phase, while on the neutral cable that provides the return path for the sum <strong>of</strong> the three line<br />

currents, the faulted condition determines almost 900A, Figure 4.12a. On the delta side, the line<br />

currents corresponding to the currents flowing in the inverter legs can be seen to barely exceed<br />

the 200A value in Figure 4.12(b). The voltage <strong>of</strong> the faulted phase on the feeder side will be zero<br />

due to the fault to ground, but due to the wye-delta connectivity two <strong>of</strong> the voltages on the delta<br />

side will be 88 percent <strong>of</strong> the original values while the third line to line voltage will be 33<br />

percent <strong>of</strong> the nominal value [7]. With the introduction <strong>of</strong> the transformer a voltage sag on the<br />

inverter side will never be lower than 33 percent <strong>of</strong> the nominal value with any kind <strong>of</strong> single<br />

line to ground faults.<br />

The transformer creates a free variable out <strong>of</strong> the DC bus since any voltage at the inverter<br />

terminals can be interfaced with the feeder voltage by an appropriate choice <strong>of</strong> the turn ratios.<br />

The ratings <strong>of</strong> the transformer must be enough to transfer all the active <strong>and</strong> reactive power that is<br />

62

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!