Size Length S<br />

[kVA]<br />

Table 6.2 Cable Data Summary.<br />

Rated V<br />

[V]<br />

Rated I<br />

[A]<br />

R o<br />

[Ω]<br />

X o<br />

[Ω]<br />

R 1<br />

[Ω]<br />

X 1<br />

[Ω]<br />

Z1 AWG 1/0 180 (ft) - 480 150 0.1889 0.0084 0.0212 0.0052<br />

Z2 AWG 3 20 (ft) 35 208 100 0.0291 0.0011 0.0049 0.00064<br />

Z3 AWG 3 75 (yd) 35 208 100 0.3277 0.0121 0.0547 0.0072<br />

Z4 AWG 3 25 (yd) 35 208 100 0.1092 0.0040 0.0182 0.0024<br />

Z2n AWG 2 20 (ft) - 208 130 0.0265 0.0010 0.0037 0.00062<br />

Z3n AWG 2 75 (yd) - 208 130 0.2979 0.0125 0.0421 0.0070<br />

Z4n AWG 2 25 (yd) - 208 130 0.0993 0.0042 0.0140 0.0023<br />

6.2.3 Loads<br />

This section describes the details <strong>of</strong> the loads present in the laboratory system.<br />

Data:<br />

The sum <strong>of</strong> the three loads must be smaller than the total output <strong>of</strong> the microsources, so that they<br />

can be supplied also in isl<strong>and</strong> mode. All loads are wye connected. Load L1 is made <strong>of</strong> two loads<br />

in parallel, one <strong>of</strong> which has the center <strong>of</strong> the star connected to the neutral, while the remaining<br />

loads have the center <strong>of</strong> the star floating. All loads have rated voltage <strong>of</strong> 208V <strong>and</strong> their overall<br />

rating is about 20kW.<br />

Load L1 through L5:<br />

All loads are connected at star: load L1 has the center star connected to the fourth wire <strong>of</strong> the<br />

system (neutral cable), while loads L2 through L5 have a floating center star, <strong>and</strong> they can be<br />

connected <strong>and</strong> disconnected with a switch. Loads are identical to each other. The data for loads<br />

is:<br />

r<br />

= r<br />

L2 L3<br />

=<br />

2<br />

3*120<br />

4000<br />

= 10.8 Ω<br />

Since the loads are purely resistive, their reactive impedance is always zero.<br />

Table 6.3 summarizes the data for all the loads present in our system.<br />

78