Figure 5.6 Unit 2- Two Units in Parallel. [50ms/div]<br />

Figure 5.7 shows the 120Hz ripple at the measured quantities <strong>of</strong> the microsource when this unit<br />

is connected to the grid <strong>and</strong> the unbalance is created by the opening <strong>of</strong> one phase. In this case the<br />

voltage unbalance measured at the terminals <strong>of</strong> the unit is <strong>of</strong> 2.82%. This is because <strong>of</strong> the stiff<br />

Thevenin impedance <strong>of</strong> the utility system being in parallel to the unbalanced load at the source.<br />

The oscillations on P <strong>and</strong> Q have a very low magnitude, while the oscillations on V have nearly<br />

completely disappeared. This allows to conclude that the source does not require any active<br />

action to compensate for negative sequences, as it has been shown that it can safely operate<br />

under the voltage unbalances below the threshold <strong>of</strong> tripping.<br />

70