Control and Design of Microgrid Components - Power Systems ...
Control and Design of Microgrid Components - Power Systems ...
Control and Design of Microgrid Components - Power Systems ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Utility<br />
System<br />
Event:<br />
Transfer to<br />
Isl<strong>and</strong><br />
F 1<br />
P 1<br />
4 wire<br />
75yd<br />
4 wire<br />
25yd<br />
P 2<br />
L L<br />
1<br />
3<br />
L4<br />
L5<br />
Figure 7.2 Series Configuration Diagram.<br />
F 2<br />
Maximum power corresponds to 0.8 pu in the source because <strong>of</strong> the DSP capability <strong>of</strong> h<strong>and</strong>ling<br />
only quantities that are in the –1,+1 interval. To leave room for overshoot, the value <strong>of</strong> P_max<br />
has been chosen to correspond to 0.8.<br />
After the system transfers to isl<strong>and</strong>, unit 2 will be sitting at 100% <strong>of</strong> power (0.8 pu), while unit 1<br />
will be sitting at 50% (since overall loading is 150%) <strong>of</strong> power (0.4 pu), in all <strong>of</strong> the four<br />
configurations. What really changes, is how they get there.<br />
Figure 7.3 <strong>and</strong> Figure 7.4 show simulation results when P1 <strong>and</strong> P2 are controlled: both units<br />
ramp up their power output (P) at the unison. Overshoot at unit 2 is near 0.89 pu (110%).<br />
Figure 7.5 <strong>and</strong> Figure 7.6 show that when F1 <strong>and</strong> F2 are controlled, then as P2 ramps, P1<br />
actually backs <strong>of</strong>f, after rising a little. This means that the resulting overshoot on P2 is about 1.04<br />
pu (130%). This implies tripping <strong>of</strong> the units, since nearly above 0.9 pu is the threshold value for<br />
power, <strong>and</strong> besides, a value larger than 1.0 is also beyond the overflow value <strong>of</strong> the bit<br />
representation inside the DSP.<br />
Figure 7.7 <strong>and</strong> Figure 7.8 show that when F1 <strong>and</strong> P2 are controlled, then an unacceptable<br />
overshoot also occurs. Figure 7.9 <strong>and</strong> Figure 7.10 show that when P1 <strong>and</strong> F2 are controlled, the<br />
overshoot is manageable again.<br />
This implies that the choice <strong>of</strong> control configurations bears a consequence on the ratings <strong>of</strong> the<br />
inverters that need to be available, or the gains may need to be readjusted (when possible) to<br />
improve response. For this lab case, the above considerations implied that the test for 10% <strong>and</strong><br />
90% could not be carried under those cases that generated very large overshoots. To avoid<br />
tripping <strong>of</strong> the units, the setpoint corresponding to loading <strong>of</strong> respectively 30% <strong>and</strong> 70% for unit<br />
1 <strong>and</strong> 2 have been chosen only for the cases with larger overshoot. This problem was only<br />
encountered during 10%, 90% setup, never during 90%, 10%, hence this latter configuration has<br />
never been changed. Also these problems are only encountered at high load levels (importing to<br />
grid). Therefore, during exporting no changes were necessary to 10%, 90% setup. Finally, no<br />
problems were encountered during the parallel configuration, so no changes had to be made there<br />
as well.<br />
The Table 7.2 below summarizes the previous considerations.<br />
94