Control and Design of Microgrid Components - Power Systems ...
Control and Design of Microgrid Components - Power Systems ...
Control and Design of Microgrid Components - Power Systems ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Chapter 2. Static Switch<br />
The static switch has the task <strong>of</strong> disconnecting all the sensitive loads from the grid once the<br />
quality <strong>of</strong> power delivered starts deteriorating. The static switch does not disconnect the local<br />
system from the grid, but it disconnects only the sensitive loads.<br />
There are two main reasons to adopt a static switch to implement the connection <strong>and</strong><br />
disconnection from the grid: first a static switch does no have mechanical moving parts,<br />
therefore its operating life will be extensively elongated compared to a traditional contactor with<br />
moving parts. The second reason to use a dedicated switch is because during reconnection with<br />
the grid a complex series <strong>of</strong> synchronization checks need to be performed. A normal interrupting<br />
breaker would be able to perform the function <strong>of</strong> disconnecting to the grid, but a sophisticated<br />
static switch is required to properly reconnect to the utility system without creating hazardous<br />
electrical transients across the microgrid.<br />
The static switch plays a key role in the interface between the microgrid <strong>and</strong> the utility system.<br />
This device needs to be controlled by a logic that verifies some constraints at the terminals <strong>of</strong> the<br />
switch before allowing for synchronization. The same logic applies to the circuitry that controls<br />
the action <strong>of</strong> the contactor, the device used to physically connect a microsource to the feeder.<br />
Disconnection at the static switch is regulated differently than at the contactor. Disconnection at<br />
the static switch takes place because <strong>of</strong> deterioration <strong>of</strong> quality <strong>of</strong> electric power delivery from<br />
the utility system. More in particular, there are at least five conditions that will enable the<br />
disconnection logic <strong>and</strong> comm<strong>and</strong> the transfer to intentional isl<strong>and</strong>:<br />
i) poor voltage quality from the utility, like unbalances due to nearby asymmetrical loads<br />
ii) frequency <strong>of</strong> the utility falls below a threshold, indicating lack <strong>of</strong> generation on the utility<br />
side<br />
iii) voltage dips that last longer than the local sensitive loads can tolerate<br />
iv) faults in the system that keep a sustained high current injection from the grid<br />
v) any current that is detected flowing from the microgrid to the utility system for a certain<br />
period <strong>of</strong> time<br />
Synchronization conditions are detected by verifying two constraints: the first is that the voltage<br />
across the switch has to be very small (ideally zero), <strong>and</strong> the second is that the resulting current<br />
after the switch is closed must be inbound from the utility system towards the microgrid. The<br />
second condition needs to be re-spelled for the case <strong>of</strong> a contactor connecting two microsources<br />
in isl<strong>and</strong> mode: in this scenario the resulting current must always be from the highest frequency<br />
source to the lower one (which is by the way the same constraint that is enforced when<br />
connecting to the grid, but there it was described using more familiar terms).<br />
2.1 Direction <strong>of</strong> Current at Synchronization<br />
The first thing that needs to be taken into consideration is that the switch is going to close on a<br />
R-L circuit that has no current previously flowing into it. Furthermore, the voltages at each <strong>of</strong> the<br />
two ends <strong>of</strong> the switch rotate at different frequencies. This implies that the relative phase angle<br />
between the voltage <strong>of</strong> the grid, E, <strong>and</strong> the voltage on the microgrid side, V, is constantly<br />
changing from a minimum value <strong>of</strong> zero degrees to a maximum <strong>of</strong> 180 <strong>and</strong> back to zero again.<br />
7