Chillers and heat pumps based on hydrocarbon refrigerants installed at Aarhus<br />
University Hospital Skejby<br />
introduction<br />
Following the ban on the installation of new R22 systems and the ban on using virgin<br />
R22 from year 2000 in Denmark the government has introduced a maximum charge<br />
when it comes to HFC of 10 kg. Multiplexing systems using 10 kg or less are not<br />
allowed unless they can be proven to be more efficient than alternatives. Furthermore<br />
the government has introduced a taxation on HFC refrigerants based on the global<br />
warming potential (GWP) values for the individual refrigerants. The tax is collected at<br />
the importers point of sale.<br />
about the system<br />
About the company<br />
Since its start in 1885, Johnson Controls has grown<br />
into a global leader in building efficiency, automotive<br />
experience, and power solutions. JCI is one of the<br />
leading companies of refrigeration and chiller solutions<br />
based on natural refrigerants. It offers products and<br />
services that optimize energy use and improve comfort<br />
and security.<br />
More information at:<br />
www.johnsoncontrols.com<br />
Contact Information<br />
Alexander Cohr Pachai<br />
Alexander.C.Pachai@jci.com<br />
(+45) 8736 7159<br />
In light of this ban and tax Aarhus University Hospital Skejby had to make a decision<br />
regarding their future chiller systems for cooling different locations aroud the hospital<br />
and also regarding the condensers of refrigeration systems in different hospital sectors<br />
and research labs.<br />
R600a R600a R744 R744<br />
40˚C/70˚C 40˚C/80˚C 40˚C/70˚C 40˚C/80˚C<br />
COP heat 3,7 3,3 2,9 2,9<br />
Assumptions Te=5˚C Te=5˚C Te=5˚C Te=5˚C<br />
Tc=68˚C Tc=78˚C Pc=110bar Pc=110bar<br />
Sc=25K<br />
Sc=25K<br />
NH 3<br />
(ammonia) was not considered as an option for the heat pumps as the technology<br />
was not developed at this point in time and will not be competitive in this size of<br />
application.<br />