Chillers and heat pumps based on hydrocarbon refrigerants installed at Aarhus<br />

University Hospital Skejby<br />

introduction<br />

Following the ban on the installation of new R22 systems and the ban on using virgin<br />

R22 from year 2000 in Denmark the government has introduced a maximum charge<br />

when it comes to HFC of 10 kg. Multiplexing systems using 10 kg or less are not<br />

allowed unless they can be proven to be more efficient than alternatives. Furthermore<br />

the government has introduced a taxation on HFC refrigerants based on the global<br />

warming potential (GWP) values for the individual refrigerants. The tax is collected at<br />

the importers point of sale.<br />

about the system<br />

About the company<br />

Since its start in 1885, Johnson Controls has grown<br />

into a global leader in building efficiency, automotive<br />

experience, and power solutions. JCI is one of the<br />

leading companies of refrigeration and chiller solutions<br />

based on natural refrigerants. It offers products and<br />

services that optimize energy use and improve comfort<br />

and security.<br />

More information at:<br />

www.johnsoncontrols.com<br />

Contact Information<br />

Alexander Cohr Pachai<br />

Alexander.C.Pachai@jci.com<br />

(+45) 8736 7159<br />

In light of this ban and tax Aarhus University Hospital Skejby had to make a decision<br />

regarding their future chiller systems for cooling different locations aroud the hospital<br />

and also regarding the condensers of refrigeration systems in different hospital sectors<br />

and research labs.<br />

R600a R600a R744 R744<br />

40˚C/70˚C 40˚C/80˚C 40˚C/70˚C 40˚C/80˚C<br />

COP heat 3,7 3,3 2,9 2,9<br />

Assumptions Te=5˚C Te=5˚C Te=5˚C Te=5˚C<br />

Tc=68˚C Tc=78˚C Pc=110bar Pc=110bar<br />

Sc=25K<br />

Sc=25K<br />

NH 3<br />

(ammonia) was not considered as an option for the heat pumps as the technology<br />

was not developed at this point in time and will not be competitive in this size of<br />

application.<br />