29.08.2014 Views

2011 Electric Service Requirements Manual, 2nd - Pacific Power

2011 Electric Service Requirements Manual, 2nd - Pacific Power

2011 Electric Service Requirements Manual, 2nd - Pacific Power

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>2011</strong> <strong>Electric</strong> <strong>Service</strong> <strong>Requirements</strong>, 2 nd Edition<br />

Section 10<br />

10.14.5 Overhead <strong>Service</strong> Termination <strong>Requirements</strong>:<br />

A switchboard service section or service section with extension shall be provided for all<br />

switchboard overhead services.<br />

Figure 10.14.5 − Overhead <strong>Service</strong> Termination, Switchboard <strong>Service</strong> Section<br />

0−600 Volts, EUSERC 348<br />

<strong>Service</strong> Section<br />

<strong>Service</strong> Section with Extension<br />

switchboard<br />

extension<br />

service entrance<br />

conductors<br />

service supply<br />

conductors<br />

90” service section<br />

(EUSERC 325 & 326)<br />

current transformer<br />

compartment<br />

to load<br />

to load<br />

<strong>Requirements</strong>:<br />

1. The service entrance conductors, cable and bus bar are furnished and installed by the<br />

customer in the following manner:<br />

a. When the switchboards are served with bus bar conductors, the conductors shall enter<br />

through the top, side or back in the upper 10” section.<br />

b. When switchboards are served with cable conductors, the conductors shall only enter the<br />

top of the switchboard.<br />

2. When conduits enter from the side or rear, an extension may be required.<br />

3. The direction of feed is from top to bottom in the switchboard service section. Load<br />

conductors shall exit below the metering compartment and may not be routed back through<br />

the current transformer compartment in order to exit the service section.<br />

This manual shall be distributed and interpreted in its entirety. Individual pages will not represent all the requirements necessary for an installation.<br />