29.08.2014 Views

2011 Electric Service Requirements Manual, 2nd - Pacific Power

2011 Electric Service Requirements Manual, 2nd - Pacific Power

2011 Electric Service Requirements Manual, 2nd - Pacific Power

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>2011</strong> <strong>Electric</strong> <strong>Service</strong> <strong>Requirements</strong>, 2 nd Edition<br />

Section 4<br />

Figure 4.2.2 − Underground Temporary Construction <strong>Service</strong> − Post<br />

1<br />

<strong>Electric</strong>al label or permit must be<br />

displayed on the meter base.<br />

6' max.<br />

4' min.<br />

Holes intended for drainage<br />

and cooling shall be kept clear.<br />

Unused mounting holes shall<br />

be covered.<br />

3<br />

grade<br />

Metal pedestals are acceptable.<br />

24” min.<br />

Ground in accordance with the<br />

latest issue of NEC Article 250.<br />

Use a minimum no. 6 copper<br />

wire for grounding.<br />

3' min.<br />

post depth<br />

24” min.<br />

service<br />

Do not locate customer<br />

conductor within 12” of<br />

utility conductor or conduit.<br />

Additional <strong>Requirements</strong>:<br />

1. The meter socket and service equipment shall be NEMA type 3R (rainproof), in good<br />

condition, with no holes, dents, or damage, and plumb in all directions. The installation shall<br />

be made with sufficient materials and installed such that it remains plumb for the duration of<br />

the temporary service.<br />

2. The customer’s minimum conductor size is No. 8 copper or No. 6 aluminum.<br />

The customer-supplied conductor shall, at minimum, be long enough to connect to the<br />

<strong>Power</strong> Company terminals.<br />

3. Conduit must be rigidly fastened to the post.<br />

4. The post is customer-owned and shall be made of pressure- or thermally-treated wood with a<br />

minimum nominal size of 4”×4”.<br />

5. A main breaker is required in post installations.<br />

6. Clearances between metallic equipment, non-metallic equipment and poles shall be<br />

maintained as specified in Section 5.5.<br />

Note: The customer also owns the conduit, conductor, and meter socket.<br />

This manual shall be distributed and interpreted in its entirety. Individual pages will not represent all the requirements necessary for an installation.<br />

15

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!