Section 5<br />
The following figures illustrate the required clearances for overhead and underground services.<br />
Figure 5.2.1 − Clearances for Buildings Supporting an Overhead <strong>Service</strong><br />
6’ max. service run<br />
over roof<br />
Optional location for<br />
gable end installations<br />
Insulated attachment<br />
required in WA and CA<br />
3/8” eye-bolt (customer<br />
provides), attached to<br />
structure of adequate<br />
strength.<br />
Insulated attachment<br />
required in WA and CA.<br />
3<br />
mast shall<br />
be within 4’<br />
of the eave<br />
3’ Min<br />
10’ max.<br />
(residential)<br />
6’ max.<br />
4’ min.<br />
3’ min.<br />
3’<br />
min.<br />
front of house<br />
Grounding per NEC Article 250<br />
<strong>Requirements</strong>:<br />
1. A ten-foot maximum distance from the front corner of a residence to the far side of the<br />
service is allowed.<br />
2. Table 5.2.1 lists the minimum drip loop and service drop clearance requirements.<br />
3. The cable and drip loop (lowest point) shall be at least 18 inches above a non-accessible roof<br />
(NESC 234.C.3.d, Exceptions 1 and 2).<br />
4. The three-foot distance between windows and the electric meter is not required if the window<br />
does not have a view of a living space or a restroom.<br />
5. The meter location must be approved by the <strong>Power</strong> Company prior to installation.<br />
6. Buildings should not be constructed under or adjacent to lines.<br />
7. For further details regarding meter clearances, see Section 5.1.<br />