<strong>2011</strong> <strong>Electric</strong> <strong>Service</strong> <strong>Requirements</strong>, 2 nd Edition<br />

Section 5<br />

The following figures illustrate the required clearances for overhead and underground services.<br />

Figure 5.2.1 − Clearances for Buildings Supporting an Overhead <strong>Service</strong><br />

6’ max. service run<br />

over roof<br />

Optional location for<br />

gable end installations<br />

Insulated attachment<br />

required in WA and CA<br />

3/8” eye-bolt (customer<br />

provides), attached to<br />

structure of adequate<br />

strength.<br />

Insulated attachment<br />

required in WA and CA.<br />

3<br />

mast shall<br />

be within 4’<br />

of the eave<br />

3’ Min<br />

10’ max.<br />

(residential)<br />

6’ max.<br />

4’ min.<br />

3’ min.<br />

3’<br />

min.<br />

front of house<br />

Grounding per NEC Article 250<br />

<strong>Requirements</strong>:<br />

1. A ten-foot maximum distance from the front corner of a residence to the far side of the<br />

service is allowed.<br />

2. Table 5.2.1 lists the minimum drip loop and service drop clearance requirements.<br />

3. The cable and drip loop (lowest point) shall be at least 18 inches above a non-accessible roof<br />

(NESC 234.C.3.d, Exceptions 1 and 2).<br />

4. The three-foot distance between windows and the electric meter is not required if the window<br />

does not have a view of a living space or a restroom.<br />

5. The meter location must be approved by the <strong>Power</strong> Company prior to installation.<br />

6. Buildings should not be constructed under or adjacent to lines.<br />

7. For further details regarding meter clearances, see Section 5.1.<br />

This manual shall be distributed and interpreted in its entirety. Individual pages will not represent all the requirements necessary for an installation.<br />

23