<strong>2011</strong> <strong>Electric</strong> <strong>Service</strong> <strong>Requirements</strong>, 2 nd Edition<br />
Section 10<br />
Figure 10.6.2 − Non-Residential Modular Meter Socket Installation<br />
customer's service<br />
entrance bus<br />
6” (or greater)<br />
depth spacer<br />
for clearance<br />
meter module<br />
permanent address labels<br />
meter module meter module meter module<br />
main<br />
disconnect<br />
(if required)<br />
pull box<br />
test blocks<br />
LINE<br />
LOAD<br />
LINE<br />
LOAD<br />
LINE<br />
LOAD<br />
breaker<br />
required<br />
breaker<br />
breaker<br />
required<br />
required<br />
TBF TBF TBF<br />
breaker<br />
required<br />
72” max.<br />
48” min.<br />
sealable<br />
enclosure<br />
24” min.<br />
final grade<br />
Notes:<br />
1. Single-phase configuration is approved.<br />
2. A vertical clearance of 36” from the surface to the center of the lowest meter is acceptable if<br />
a 3-foot wide, flat, permanent surface (such as a concrete pad or walkway) below the meter is<br />
provided at the final grade.<br />
Figure 10.6.3 − Non-Residential Switch Board Metering<br />
(Direct−Connect, Floor Mounted)<br />
EUSERC 306<br />
pull box<br />
12” min.<br />
permanent<br />
address labels<br />
TBF<br />
TBF<br />
TBF<br />
TBF<br />
ÉÉ<br />
ÉÉ<br />
É<br />
É<br />
TBF<br />
TBF<br />
TBF<br />
TBF<br />
TBF<br />
TBF<br />
TBF<br />
TBF<br />
ÉÉ<br />
ÉÉ<br />
É<br />
É<br />
TBF<br />
TBF<br />
TBF<br />
TBF<br />
Labeled service<br />
breakers are required<br />
for each service.<br />
The position of the<br />
breaker on the panel<br />
is determined by the<br />
manufacturer.<br />
TBF<br />
TBF<br />
TBF<br />
TBF<br />
ÉÉ<br />
ÉÉ<br />
ÉÉ<br />
ÉÉ<br />
ÉÉ<br />
É<br />
É<br />
É<br />
É<br />
É<br />
TBF<br />
TBF<br />
TBF<br />
TBF<br />
36” min.<br />
75” max.<br />
concrete pad<br />
multiple meter section<br />
6” min. spacers<br />
multiple meter section<br />
ÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂ<br />
ÉÉ É<br />
ÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂ<br />
Notes:<br />
a. The customer must provide a concrete pad for switchboard metering service sections<br />
and pull boxes.<br />
b. A single-phase configuration is acceptable.<br />
This manual shall be distributed and interpreted in its entirety. Individual pages will not represent all the requirements necessary for an installation.<br />
77