Section 7<br />

<strong>2011</strong> <strong>Electric</strong> <strong>Service</strong> <strong>Requirements</strong>, 2 nd Edition<br />

Figure 7.7.1 − Underground <strong>Service</strong> to Dwellings with Permanent Foundations<br />

Ç<br />

Ç<br />

Meter Attached to Dwelling (UG)<br />

Meter to Overhead Transformer<br />

3' Min.<br />

10' Max.<br />

6’ Max.<br />

4’ Min.<br />

The customer<br />

provides the trench,<br />

conduit and sweeps.<br />

All above‐ground<br />

conduit shall meet the<br />

NEC requirement of<br />

Schedule 40 or better.<br />

The sweep is provided by the customer<br />

and installed as directed by the <strong>Power</strong><br />

Company. Conduit and the pole (at ground<br />

line) shall have 8” of separation.<br />

24” Min.<br />

24” Min.<br />

Customer<br />

installed conduit<br />

<strong>Power</strong> Company<br />

installed equipment<br />

Meter to Underground Transformer Vault<br />

Meter to Secondary Junction Box<br />

The <strong>Power</strong> Company‐owns<br />

and installs the transformer<br />

and the cable.<br />

The sweep is provided by the<br />

customer and installed by the<br />

<strong>Power</strong> Company.<br />

junction box<br />

24” min.<br />

The customer provides<br />

the conduit and the vault.<br />

The conduit is glued to<br />

the vault by the customer.<br />

Customer<br />

installed conduit<br />

<strong>Power</strong> Company<br />

installed equipment<br />

44<br />

This manual shall be distributed and interpreted in its entirety. Individual pages will not represent all the requirements necessary for an installation.