PART 3: SECTION 8.2<br />

FLEXIBLE DROPS<br />

The Viking Corporation<br />

210 N Industrial Park, Hastings, Michigan 49058, USA<br />

Tel: +1 269 945 9501 • Fax: +1 269 945 9599<br />

E-mail: techsvcs@vikingcorp.com • Website: www.vikingcorp.com<br />

UK Sales Contact<br />

Viking SupplyNet Ltd, G6 Bellwin House, Bellwin Drive, Flixborough Industrial Estate, Flixborough, North<br />

Lincolnshire DN15 8SN, United Kingdom<br />

Tel: +44 (0) 1724 295 300 • Fax: +44 (0) 1724 295 301<br />

E-mail: vikinguk@vikingcorp.com<br />

Certificate No: 096i/01<br />

Viking Flex Drop - 28mm Braided<br />

Product Name Length mm Inlets Outlet MWP Bar LPCB Ref. No.<br />

VKFD28 B-07 700 1" NPT 1/2" NPT or BSPT 17.2 096i/01<br />

VKFD28 B-10 1000 1" BSPT 3/4" NPT or BSPT<br />

VKFD28S B-12 1200 1 1/4" NPT Female Straight<br />

VKFD28 B-15 1500 1 1/4" BSPT 90 degree Angle<br />

VKFD28 B-18 1800 Male<br />

These products have been approved as a Type 2 hose of moderate flexibility in accordance with LPS 1261. These may be used in<br />

applications where little or no differential movement between the two ends is expected after installation (e.g. supply to single <strong>sprinkler</strong>s in<br />

suspended ceilings)<br />

1) Viking Flex Drop <strong>sprinkler</strong> connections are approved for use in the following applications:<br />

Hose diam<br />

(mm)<br />

28<br />

Length Pre-calculated Fully hydraulically<br />

(mm) Town’s Pumped calculated<br />

700 Yes Yes Yes<br />

1000 Yes Yes Yes<br />

1200 Yes Yes Yes<br />

1500 Yes Yes Yes<br />

1800 Yes Yes Yes<br />

All pipework supplying Viking Flex Drop <strong>sprinkler</strong> connection assemblies in pre-calculated <strong>systems</strong> shall be sized as distribution<br />

mains.<br />

The above restrictions apply to Viking Flex Drops with any configuration of inlet <strong>and</strong> outlet fittings <strong>and</strong> apply with up to three 90°<br />

bends (excluding a 90 angled outlet nipple).<br />

2) In suspended ceiling Viking Flex Drop flexible <strong>sprinkler</strong> drops must be installed in accordance with Viking Installation manuals<br />

VKFD28-LPCB-CLIP or Installation manual 112107<br />

3) In suspended ceilings, outlet reducer must be secured to the ceiling support system with brackets supplied. For other applications the<br />

installer must supply brackets to ensure <strong>sprinkler</strong> is secure.<br />

Certificate No: 096i/02<br />

Viking Flex Drop - 28mm UnBraided<br />

Product Name Length mm Inlets Outlet MWP Bar LPCB Ref. No.<br />

VKFD28 U-07 700 1" NPT 1/2" NPT or BSPT 13.8 096i/02<br />

VKFD28 U-10 1000 1" BSPT 3/4" NPT or BSPT<br />

VKFD28 U-12 1200 1 1/4" NPT Female, Straight<br />

VKFD28S U-15 1500 1 3/4" BSPT 90 degree Angle<br />

& 90 degree Angle<br />

& 90 degree Angle<br />

& 90 degree Angle<br />

& 90 degree Angle<br />

& 90 degree Angle<br />

& 90 degree Angle<br />

VKFD28 U-18 1800 Male<br />

18 Jan 2014 91