PART 3: SECTION 21.1<br />

PLASTIC PIPES AND FITTINGS<br />

Product Name Size Model Maximum LPCB Ref. No.<br />

Working<br />

Pressure<br />

(bar)<br />

1" 12<br />

1¼" 12<br />

1½" 12<br />

2" 12<br />

CPVC Union (Soc x Soc) ¾" V5033-E 12 878a/21<br />

1" V5033-E 12<br />

CPVC Union (Soc x Thd) w/ Brass End ¾" V5033-E-3 12<br />

1" V5033-E-3 12<br />

Grooved Coupling 1¼" V5001-G 12 878a/22<br />

1½" V5001-G 12<br />

2" V5001-G 12<br />

2½" V5001-G 12<br />

65mm x 2½" V5001-G 12<br />

3" V5001-G 12<br />

Notes relating to Viking Plastics fittings:<br />

1) Viking Plastics Fittings are LPCB approved for use with Viking Plastics <strong>and</strong> Harvel LPCB approved pipes <strong>and</strong> Nibco FP-1000 “One-<br />

Step Solvent Cement” adhesive.<br />

2) Where assemblies are made using Harvel pipe, the system of pipe <strong>and</strong> fittings must be installed in accordance with Nibco Inc<br />

Installation Instructions ( Nibco Ref: IM-BLZME-0608 dated 19/05/08). which includes LPCB Conditions of Use agreed with Nibco<br />

3) Where assemblies are made using Viking pipe, the system of pipe <strong>and</strong> fittings must be installed in accordance with Nibco Inc<br />

Installation Instructions (Nibco Ref: IM-BLZME-0608 dated 19/05/08) <strong>and</strong> Viking Plastics 'Blazemaster' Installation Instruction (Viking<br />

Ref: VBM020107 Revision 4) which includes LPCB Conditions of Use agreed with Nibco <strong>and</strong> Viking<br />

4) The maximum normal ambient temperature of use shall not exceed 50°C.<br />

5) The products shall only be installed by LPCB Certificated or Registered installing companies (see Part 5, Section 1A <strong>and</strong> 1B above),<br />

or by firms outside the UK who can provide evidence of personnel training in the installation of the product. It is recommended that<br />

firms engaged in the installation of this product also be LPCB Certificated to ISO 9000.<br />

6) Viking Plastics Blazemaster CPVC fittings are manufactured from Blazemaster CPVC materials that are WRAS listed.<br />

7) Blazemaster® is a registered trademark of Lubrizol Advanced Materials, Inc.<br />