PART 3: SECTION 21.1<br />

PLASTIC PIPES AND FITTINGS<br />

This section lists products approved in accordance with:<br />

<br />

LPS 1260 Requirements for testing plastic pipes <strong>and</strong> fittings for <strong>sprinkler</strong> <strong>systems</strong>.<br />

The ‘scope of use’ of plastic pipe shall be agreed between the plastics suppliers, purchaser/installer, authority<br />

having jurisdiction <strong>and</strong>/or insurer in accordance with documented supplier ‘Installation Instructions’ but subject<br />

to the following criteria taking precedence.<br />

1) Use of plastic pipe <strong>and</strong> fittings is subject to <strong>water</strong> authority agreement for the district or territory concerned.<br />

2) LPCB Approved quick response <strong>sprinkler</strong>s shall be used with exposed (i.e. fire exposure) plastic pipe <strong>and</strong><br />

fittings.<br />

3) Plastic pipe <strong>and</strong> fittings are suitable for use only with wet pipe <strong>systems</strong>.<br />

4) Use of <strong>water</strong> additives is only permitted in accordance with the manufacturer’s installation instructions.<br />

5) Care should be exercised to ensure that the adhesive joints are adequately cured, in accordance with the<br />

manufacturer’s installation instructions, prior to pressurisation.<br />

6) Plastic pipe <strong>and</strong> fittings shall not be installed outdoors.<br />

7) Where plastic pipe <strong>and</strong> fittings are exposed (i.e. fire exposure), the system shall be installed close to a flat<br />

ceiling construction.<br />

8) Sprinkler <strong>systems</strong> which employ plastic pipe <strong>and</strong> fittings shall be designed where possible to ensure there<br />

are no ‘no flow’ sections of pipework in the event of <strong>sprinkler</strong> operation.<br />

Aquatherm GmbH<br />

Biggen 5, D-57439 Attendorn, Germany<br />

Tel: +49 2722 950223 • Fax: +49 2722 950252<br />

E-mail: info@aquatherm.de • Website: www.aquatherm.de<br />

Certificate No: 684a to LPS 1260<br />

Aquatherm GmbH 'Red Pipe' PPR Plastic Pipe & Fittings<br />

Product Name<br />

Nominal Diameter<br />

Range<br />

(mm)<br />

Maximum<br />

Working<br />

Pressure<br />

(bar)<br />

LPCB Ref.<br />

No.<br />

'Red Pipe' Sprinkler Pipe 20,25,32,40,50,63,75,90,110,125 12 684a/01<br />

Socket 20,25,32,40,50,63,75,90,110,125 12 684a/02<br />

Reducer 20,25,32,40,50,63,75,90,110,125 12 684a/03<br />

Elbow, 90° 20,25,32,40,50,63,75,90,110,125 12 684a/04<br />

Elbow, 45° 20,25,32,40,50,63,75,90,110,125 12 684a/05<br />

Tee 20,25,32,40,50,63,75,90,110,125 12 684a/06<br />

Reducing Tee<br />

20x25x20;25x20x20;25x20x25;32x20x20;<br />

12 684a/07<br />

32x20x32;32x25x32;40x20x40;40x25x40;<br />

40x32x40;50x20x50;50x25x50;50x32x50;<br />

50x40x50;63x40x63;63x50x63;75x40x75;<br />

75x50x75;75x63x75;90x40x90;90x50x90;<br />

90x63x90;90x75x90;110x63x110;110x75x110;<br />

110x90x110;125x75x125;125x90x125;125x110x125<br />

End Cap 20,25,32,40,50,63,75,90,110,125 12 684a/08<br />

Socket Welded Nipple 32,40,50,63,75,90,110,125 12 684a/09<br />

Saddle Weld-in 40/20;40/25;50/20;50/25;63/20;63/25;63/32;75/20;<br />

12 684a/10<br />

75/25;75/32;90/20;90/25;90/32;90/40;110/20;110/25;<br />

110/32;110/40;125/20;125/25;125/32;125/40<br />

Coupling screw joint 32,40,50,63,75 12 684a/11<br />

Wall connection 20x1/2"F;25x3/4"F 12 684a/12<br />