PART 3: SECTION 22<br />
METRON ACTUATORS<br />
This section lists products approved in accordance with:<br />
<br />
LPCB Schedule of requirements<br />
Metron actuators listed below have been evaluated in relation to their general performance capability but not<br />
in relation to their suitability for specific applications.<br />
LPCB strongly recommends that:<br />
1) Care shall be exercised to ensure that the monitoring current specified by the manufacturer is not<br />
exceeded.<br />
2) The manufacturer’s installation instructions <strong>and</strong> product safety instructions shall be followed.<br />
3) These devices shall be replaced every ten years.<br />
Chemring Energetics Limited<br />
Ardeer Site, Stevenston, Ayrshire, Scotl<strong>and</strong> KA20 3LN, United Kingdom<br />
Tel: +44 (0)1294 487007 • Fax: +44 (0)1294 487230<br />
E-mail: campbell.howie@chemringenergetics.co.uk • Website: www.chemringenergetics.co.uk<br />
Certificate No: 313a<br />
Protractor ‘Metron’ Actuators<br />
Product<br />
Name<br />
Stroke<br />
(mm)<br />
Work Outout J<br />
(minimum)<br />
Resistance Range<br />
Ohms<br />
Allfire Amps<br />
(50ms)<br />
Nofire Amps (5<br />
sec)<br />
LPCB Ref.<br />
No.<br />
DR2001/C13 3.4 0.69 0.9 to 1.6 0.6 0.3 313a/01<br />
DR2003/C1 3.4 1.18 0.9 to 1.6 0.6 0.3 313a/02<br />
DR2003/C6 3.4 1.18 0.9 to 1.6 0.6 0.3<br />
DR2003/C35 3.4 1.18 0.9 to 1.6 0.6 0.3<br />
DR2004/C1 9.5 3.43 0.9 to 1.6 0.6 0.3 313a/03<br />
DR2005/C1 9.5 3.43 0.9 to 1.6 0.6 0.3 313a/04<br />
DR2005/C2 9.5 3.43 0.9 to 1.6 0.6 0.3<br />
DR2005/C3 9.5 3.43 0.9 to 1.6 0.6 0.3<br />
DR2005/C6 9.5 3.43 0.9 to 1.6 0.6 0.3<br />
DR2005/C9 9.5 3.43 0.9 to 1.6 0.6 0.3<br />
DR2005/C35 9.5 3.43 0.9 to 1.6 0.6 0.3<br />
DR2006/C1 13.5 4.9 0.9 to 1.6 0.6 0.3 313a/05<br />
DR2006/C2 13.5 4.9 0.9 to 1.6 0.6 0.3<br />
DR2014/C1 9.5 4.9 0.9 to 1.6 0.6 0.3 313a/06<br />
DR2053 3.4 0.8 7 to 12 0.16 0.05 313a/07<br />
Maximum monitoring current for all models is 0.01A.<br />
186 18 Jan 2014