PART 3: SECTION 22<br />

METRON ACTUATORS<br />

This section lists products approved in accordance with:<br />

<br />

LPCB Schedule of requirements<br />

Metron actuators listed below have been evaluated in relation to their general performance capability but not<br />

in relation to their suitability for specific applications.<br />

LPCB strongly recommends that:<br />

1) Care shall be exercised to ensure that the monitoring current specified by the manufacturer is not<br />

exceeded.<br />

2) The manufacturer’s installation instructions <strong>and</strong> product safety instructions shall be followed.<br />

3) These devices shall be replaced every ten years.<br />

Chemring Energetics Limited<br />

Ardeer Site, Stevenston, Ayrshire, Scotl<strong>and</strong> KA20 3LN, United Kingdom<br />

Tel: +44 (0)1294 487007 • Fax: +44 (0)1294 487230<br />

E-mail: campbell.howie@chemringenergetics.co.uk • Website: www.chemringenergetics.co.uk<br />

Certificate No: 313a<br />

Protractor ‘Metron’ Actuators<br />

Product<br />

Name<br />

Stroke<br />

(mm)<br />

Work Outout J<br />

(minimum)<br />

Resistance Range<br />

Ohms<br />

Allfire Amps<br />

(50ms)<br />

Nofire Amps (5<br />

sec)<br />

LPCB Ref.<br />

No.<br />

DR2001/C13 3.4 0.69 0.9 to 1.6 0.6 0.3 313a/01<br />

DR2003/C1 3.4 1.18 0.9 to 1.6 0.6 0.3 313a/02<br />

DR2003/C6 3.4 1.18 0.9 to 1.6 0.6 0.3<br />

DR2003/C35 3.4 1.18 0.9 to 1.6 0.6 0.3<br />

DR2004/C1 9.5 3.43 0.9 to 1.6 0.6 0.3 313a/03<br />

DR2005/C1 9.5 3.43 0.9 to 1.6 0.6 0.3 313a/04<br />

DR2005/C2 9.5 3.43 0.9 to 1.6 0.6 0.3<br />

DR2005/C3 9.5 3.43 0.9 to 1.6 0.6 0.3<br />

DR2005/C6 9.5 3.43 0.9 to 1.6 0.6 0.3<br />

DR2005/C9 9.5 3.43 0.9 to 1.6 0.6 0.3<br />

DR2005/C35 9.5 3.43 0.9 to 1.6 0.6 0.3<br />

DR2006/C1 13.5 4.9 0.9 to 1.6 0.6 0.3 313a/05<br />

DR2006/C2 13.5 4.9 0.9 to 1.6 0.6 0.3<br />

DR2014/C1 9.5 4.9 0.9 to 1.6 0.6 0.3 313a/06<br />

DR2053 3.4 0.8 7 to 12 0.16 0.05 313a/07<br />

Maximum monitoring current for all models is 0.01A.<br />