PART 3: SECTION 9.1<br />

PRE-ACTION CONTROL SYSTEMS<br />

Victaulic Company<br />

4901 Kesslersville Road, Easton, Pennsylvania 18040, USA<br />

Tel: +1 610 559 3300 • Fax: +1 610 250 8817<br />

E-mail: victaulic@victaulic.com • Website: www.victaulic.com<br />

Certificate No: 104k<br />

Victaulic Series 769 Pre-Action System (Pre-action Control Valve Description)<br />

Product Name Nominal Size Mounting<br />

Attitude<br />

Body<br />

Material<br />

Type Max Working<br />

Pressure<br />

(bar)<br />

Series 769 Single Interlock<br />

(Electric)<br />

Series 769 Single Interlock<br />

(Pneumatic/Electric)<br />

Series 769 Double<br />

Interlock<br />

40, 50, 65, 76.1,<br />

80, 100, 150,<br />

165.1, 200<br />

40, 50, 65, 76.1,<br />

80, 100, 150,<br />

165.1, 200<br />

40, 50, 65, 76.1,<br />

80, 100, 150,<br />

165.1, 200<br />

Vertical Cast Iron Preaction<br />

Vertical Cast Iron Preaction<br />

Vertical Cast Iron Preaction<br />

Connections<br />

LPCB<br />

Ref. No.<br />

20 Grooved 104k/01<br />

20 Grooved 104k/02<br />

20 Grooved 104k/03<br />

Notes:<br />

1) The above <strong>systems</strong> are approved also when configured with ‘Autoconvert’ option.<br />

Approval Conditions:<br />

1) The above pre-action system employs duplicate solenoid valves, which are manufactured by firms, as detailed below. One of each<br />

shall be used.<br />

2) Solenoid valves shall be installed in parallel.<br />

3) Solenoid valves shall function in pneumatic condition only, <strong>and</strong> be protected by a strainer.<br />

4) LPCB Certificated detectors compatible with the control <strong>and</strong> indicating equipment shall be used.<br />

5) Suitable electrical detection control <strong>and</strong> indicating equipment <strong>and</strong> pneumatic <strong>systems</strong> which are compatible with the equipment<br />

identified above shall be used. The control <strong>and</strong> indicating equipment should be LPCB approved/certificated.<br />

6) Connecting cables shall comply with BS 6387: 1994, classification C, W, Z evidenced by LPCB certification.<br />

7) The system shall be electrically monitored to demonstrate that it is in a ‘ready-to-operate’ state at all times.<br />

8) Clean dry air shall be used.<br />

9) The equipment must be installed, operated <strong>and</strong> maintained as prescribed in Victaulic installation, maintenance <strong>and</strong> testing manuals “I-<br />

769P revision D” <strong>and</strong> “I-769P-EPA revision D”.<br />

10) The pre-action <strong>systems</strong> shall comply with the details specified in LPC Rules for <strong>Automatic</strong> <strong>sprinkler</strong> <strong>systems</strong> Technical Bulletin 21 or<br />

208 Supplementary Requirements for <strong>sprinkler</strong> installations which can operate in the dry mode <strong>and</strong> in the LPC Rules for <strong>Automatic</strong><br />

Sprinkler Installations.<br />

11) Victaulic Company are the firm responsible for the complete pre-action station, including electrics. It should be noted that only the<br />

equipment specifically referenced above is LPCB approved.<br />

Victaulic Pre-Action System (Solenoid Valve Description)<br />

Product Name Manufacturer Voltage (V) Power (W) LPCB Ref. No.<br />

Series 753E Spartan Scientific 24 DC 10.0 104k/04<br />

8210P007 ASCO 24 DC 2.0 104k/05<br />