Automatic sprinkler, water spray and deluge systems - RedBookLive
Automatic sprinkler, water spray and deluge systems - RedBookLive
Automatic sprinkler, water spray and deluge systems - RedBookLive
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
PART 3: SECTION 3.1<br />
WET AND DRY ALARM VALVES FOR SPRINKLER SYSTEMS<br />
Venus Fire Protection Ltd<br />
4105, Portl<strong>and</strong> Blvd, Sherbrooke (Quebec) J1L 1X9, Canada<br />
Tel: +1 819 820 8000 • Fax: +1 819 820 8002<br />
E-mail: venus@venus.ca • Website: www.venus-fire.com<br />
Certificate No: 638a to EN 12259-2:1999 + Amendment A1:2001 & Amendment A2: 2005<br />
Wet Alarm Valve<br />
Product Name Model Sizes<br />
LPCB Ref. No.<br />
(mm)<br />
Wet Alarm Valve B 80, 100, 150, 200 (1, 2, 3, 4) 638a/01<br />
D 100, 150, 200 (1, 2, 3, 5) 638a/02<br />
E 100, 150, (1, 2, 3, 6) 638a/03<br />
Notes:<br />
1) Approved for use in vertical mounting position only.<br />
2) Maximum working pressure 12 bar.<br />
3) Approved for use with <strong>and</strong> without Model E Retard Chamber.<br />
4) With flanged inlet <strong>and</strong> flanged outlet.<br />
5) With flanged inlet <strong>and</strong> grooved outlet.<br />
6) With grooved inlet <strong>and</strong> grooved outlet.<br />
Victaulic Company<br />
4901 Kesslersville Road, Easton, Pennsylvania 18040, USA<br />
Tel: +1 610 559 3300 • Fax: +1 610 250 8817<br />
E-mail: victaulic@victaulic.com • Website: www.victaulic.com<br />
Certificate No: 104c to EN 12259-3<br />
Series 768<br />
Product Name Model Sizes<br />
LPCB Ref. No.<br />
(mm)<br />
Series 768 Dry Alarm Valve Series 40, 50, 65, 80, 100, 150 & 200 104c/01<br />
Notes:<br />
1) Maximum working pressure: 20 bar.<br />
2) Approved for use with <strong>and</strong> without Victaulic Series 746 LPA accelerator.<br />
3) Approved with grooved inlet <strong>and</strong> outlet only.<br />
4) Approved in vertical orientation only.<br />
5) Installations containing Series 768 valve shall be maintained under servicing contracts with the manufacturer, or LPS 1048 <strong>and</strong> LPS<br />
1050 firms experienced in the installation <strong>and</strong> servicing of this valve.<br />
Certificate No: 104e to EN 12259-2<br />
Series 751<br />
Product Name Model Sizes LPCB Ref. No.<br />
Series 751 Wet Alarm Valve Series 751 80, 100, 150 & 200 104e/01<br />
Notes:<br />
1) Maximum working pressure: 16 bar<br />
2) Approved for use with <strong>and</strong> without Series 752 retard chamber.<br />
3) Approved with grooved inlet <strong>and</strong> outlet only.<br />
4) Approved in vertical orientation only.<br />
5) 150mm nominal diameter valve approved in 165.1mm <strong>and</strong> 168.3mm outside diameters.<br />
6) Installations containing Series 751 valve shall be maintained under servicing contracts with the manufacturer, or LPS 1048 <strong>and</strong> LPS<br />
1050 firms experienced in the installation <strong>and</strong> servicing of this valve.<br />
36 18 Jan 2014