PART 3: SECTION 9.1<br />

PRE-ACTION CONTROL SYSTEMS<br />

9) The equipment must be installed, operated <strong>and</strong> maintained as prescribed in Angus Fire Ltd. installation, operating <strong>and</strong><br />

maintenance manual.<br />

10) The pre-action system shall be configured in accordance with Angus specification numbers, PA1/100 <strong>and</strong> PA1/150 for the 100mm<br />

<strong>and</strong> 150mm versions respectively.<br />

11) The Pre-Action <strong>systems</strong> shall comply with the details specified in LPC Technical Bulletin 21 Supplementary requirements for <strong>sprinkler</strong><br />

installations which can operate in the dry mode.<br />

12) Angus Fire, Denmark, is responsible for the complete pre-action system.<br />

The Reliable <strong>Automatic</strong> Sprinkler Co., Inc,<br />

1470 Smith Grove Road, Liberty, South Carolina 29657, USA<br />

Tel: +1 864 843 1734 • Fax: +1 864 843 1418<br />

E-mail: jcevallos@reliable<strong>sprinkler</strong>.com • Website: www.reliable<strong>sprinkler</strong>.com<br />

UK Sales Enquiries<br />

Tel: +44 (0)1372 728899 • Fax: +44 (0)1372 724461<br />

Certificate No: 034d<br />

Certificate No: 034M<br />

RELIABLE SINGLE INTERLOCK PRE-ACTION SYSTEM (Pre-action Control Valve Description)<br />

Product Name Size(s) Mounting Attitude Body Material Type Maximum Flanged LPCB Ref. No.<br />

(mm)<br />

Working<br />

Pressure<br />

or Grooved<br />

BX/E 100 Vertical Cast Iron Pre-action 12 bar Flanged 034d/01<br />

150 Vertical Cast Iron Pre-action 12 bar Flanged<br />

DDX 4" 100 Verticle Ductile Iron Pre-action 17.2 Grooved 034M/01<br />

DDX 6" 150 Verticle Ductile Iron Pre-action 17.2 Grooved 034m/01<br />

DDX 165mm 165 Verticle Ductile Iron Pre-action 17.2 Grooved<br />

Approval Conditions:<br />

1) The above pre-action system employs duplicate solenoid valves, which are manufactured by firms, as detailed below. One of each<br />

shall be used.<br />

2) Solenoid valves shall be installed in parallel.<br />

3) Solenoid valves shall function in pneumatic condition only, <strong>and</strong> be protected by a strainer.<br />

4) LPCB Certificated detectors compatible with the control <strong>and</strong> indicating equipment shall be used.<br />

5) Suitable electrical detection control <strong>and</strong> indicating equipment <strong>and</strong> pneumatic <strong>systems</strong> which are compatible with the equipment<br />

identified above shall be used. The control <strong>and</strong> indicating equipment should be LPCB approved/certificated.<br />

6) Connecting cables shall comply with BS 6387: 1994, classification C, W, Z evidenced by LPCB certification.<br />

7) The system shall be electrically monitored to demonstrate that it is in a ‘ready-to-operate’ state at all times.<br />

8) Clean dry air shall be used.<br />

9) The equipment must be installed, operated <strong>and</strong> maintained as prescribed in The Reliable <strong>Automatic</strong> Sprinkler Co Inc installation,<br />

operating <strong>and</strong> maintenance manuals “Bulletin 717 revision C” <strong>and</strong> “Bulletin 739 revision A”.<br />

11) The pre-action <strong>systems</strong> shall comply with the details specified in LPC Rules for <strong>Automatic</strong> <strong>sprinkler</strong> <strong>systems</strong> Technical Bulletin 21 or<br />

208 Supplementary Requirements for <strong>sprinkler</strong> installations which can operate in the dry mode <strong>and</strong> in the LPC Rules for <strong>Automatic</strong><br />

Sprinkler Installations.<br />

12) The Reliable <strong>Automatic</strong> Sprinkler Company Inc are the firm responsible for the complete pre-action station, including electrics. It<br />

should be noted that only the equipment specifically referenced above is LPCB approved.<br />

Certificate No: 034d<br />

RELIABLE SINGLE INTERLOCK PRE-ACTION SYSTEM (Solenoid Valve Description)<br />

Product Name Manufacturer Voltage (V) Power (W) LPCB Ref. No.<br />

LV2LBX25 Skinner 24 DC 11 034d/01<br />

R8210A107 ASCO 24 DC 10.6<br />

Approval Conditions:<br />

1) The above pre-action system employs duplicate solenoid valves, which are manufactured by firms, as detailed above. One of<br />

each shall be used.<br />

2) Solenoid valves shall be installed in parallel.<br />

3) Solenoid valves shall function in pneumatic condition only, <strong>and</strong> be protected by a strainer.<br />

4) LPCB Certificated detectors compatible with the control <strong>and</strong> indicating equipment shall be used.<br />

5) Suitable electrical detection control <strong>and</strong> indicating equipment <strong>and</strong> pneumatic <strong>systems</strong> which are compatible with the equipment<br />

identified above shall be used. The control <strong>and</strong> indicating equipment should be LPCB approved/certificated.<br />

18 Jan 2014 103