Automatic sprinkler, water spray and deluge systems - RedBookLive
Automatic sprinkler, water spray and deluge systems - RedBookLive
Automatic sprinkler, water spray and deluge systems - RedBookLive
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
PART 3: SECTION 13.1<br />
LPS 1276 TANKS<br />
(b) an equivalent corrosion protection system which has been specifically approved <strong>and</strong> listed by the LPCB, with such tank entries<br />
marked ‘e’.<br />
5. The purchaser shall specify the required tank designation “Superior” or “Single” in accordance with the LPC Rules for <strong>Automatic</strong><br />
Sprinkler Installations, together with the tank reference number.<br />
6. The tank must bear a plate stating:<br />
(i) The name <strong>and</strong> address of the manufacturer.<br />
(ii) The date of installation.<br />
(iii) The LPCB Reference Number, including the type suffix (“Superior” or “Single”) which has been specified by the purchaser <strong>and</strong><br />
agreed by the manufacturer.<br />
(iv) The maximum capacity in cubic metres. Multi-supply tanks must indicate the capacity for the automatic <strong>sprinkler</strong> system separately.<br />
Tanks which do not bear such a plate are not approved.<br />
7. Specifiers of LPCB approved <strong>sprinkler</strong> suction tanks are advised to ensure that where a vortex inhibitor is used in accordance with the<br />
LPC Sprinkler Rules, that the vortex inhibitor used is listed in Part 5 Section 14 of the Red Book as LPCB approved.<br />
8. Where “Superior” tank shell exteriors are not protected by 610g/m 2 or equivalent, appropriate inspection, service <strong>and</strong> maintenance<br />
shall be specified. Exterior shell protection of 300g/m 2 galvanising is set as the minimum acceptable level of exterior protection coupled<br />
with specified inspection service <strong>and</strong> maintenance.<br />
9. Immersion heaters used to prevent the ball valve <strong>and</strong> <strong>water</strong> in the vicinity from freezing shall be dual element type.<br />
CST Industries (UK) Limited<br />
Cotes Park Lane, Cotes Park Industrial Estate, Alfreton, Derbyshire DE55 4NJ, United Kingdom<br />
Tel: +44 (0)1773 835321 • Fax: +44 (0)1773 836578<br />
E-mail: ukinfo@cstindustries.com • Website: www.cstindustries.com<br />
Certificate No: 044c/01 to LPS1276 1.1<br />
Certificated Products<br />
Single supply tank<br />
Superior supply tank<br />
Single supply tank<br />
Superior Supply Tank<br />
Single supply tank<br />
Superior supply tank<br />
LPCB Ref.<br />
No.<br />
Bolted cylindrical, mastic sealed, galvanized steel plate tank with a galvanized steel 044c/01<br />
decking cover that is externally coated with PVC.<br />
Maximum capacity 1300m 3<br />
Bolted cylindrical, mastic sealed, galvanized steel plate tank with a galvanized steel 044c/02g<br />
decking cover that is externally coated with PVC.<br />
Maximum capacity 1300m 3<br />
Bolted rectangular, mastic sealed galvanized steel panel tank with a galvanized steel 044cc/03<br />
decking cover. Suitable for restricted space locations. Designed to most shapes using 90<br />
degree corners <strong>and</strong> up to 3m in height.<br />
Maximum capacity 1300m 3<br />
Bolted rectangular, mastic sealed galvanized steel panel tank with a galvanized steel 044c/04e<br />
decking cover. Suitable for restricted space locations. Designed to most shapes using 90<br />
degree corners <strong>and</strong> up to 3m in height.<br />
Maximum capacity 1300m 3<br />
Bolted cylindrical, rubber liner sealed, galvanized steel plate tank with a galvanized steel 044c/05<br />
decking cover that is externally coated with PVC.<br />
Maximum capacity 1300m 3<br />
Bolted cylindrical, rubber liner sealed, galvanized steel plate tank with a galvanized steel 044c/06e<br />
decking cover that is externally coated with PVC.<br />
Maximum capacity 1300m 3<br />
Notes:<br />
All tank approvals are strictly subject to tanks being supplied in accordance with LPCB Approved Conditions set out in the ‘Introduction’.<br />
For galvanized steel tanks, Type “Superior”, the designation ‘g’ refers to tanks protected by 610g/m 2 each side <strong>and</strong> the designation 'e'<br />
refers to equivalent corrosion protection as set out in Item 4 of the Introduction.<br />
128 18 Jan 2014