PART 3: SECTION 11.2<br />

ELECTRICALLY OPERATED SPRINKLER HEADS<br />

This section lists products approved in accordance with:<br />

<br />

LPCB Schedule of requirements<br />

Sprinkler Heads included in this section include a means of electronic operation in addition to the normal glass<br />

bulb mode.<br />

Approval Conditions<br />

1) LPCB approved detectors compatible with the control <strong>and</strong> indicating equipment shall be used;<br />

2) Suitable electrical detection control <strong>and</strong> indicating equipment compatible with the equipment below shall be<br />

used. The control <strong>and</strong> indicating equipment shall be LPCB Approved/Certificated;<br />

3) Connecting cables shall comply with BS 6387:1994 Specification for performance requirements for cables<br />

required to maintain circuit integrity under fire conditions, classification C,W,Z or equivalent;<br />

4) The equipment must be installed, operated <strong>and</strong> maintained as prescribed in the manufacturer's Installation,<br />

Operating <strong>and</strong> Maintenance Manual;<br />

5) To guard against inadvertent operation it is recommended that electrically operated <strong>sprinkler</strong>s be used in<br />

conjunction with coincidence detection;<br />

6) Where ‘Metron’ actuators are employed the maximum allowable operating temperature shall not be<br />

exceeded;<br />

7) Where ‘Metron’ actuators are used, these shall also be LPCB approved; <strong>and</strong><br />

8) The ‘Guidance’ in the Part 3 Section 22 ‘Metron’ Actuators, shall also be taken into account.<br />

GW Sprinkler A/S<br />

Kastanievej 15, DK-5620 Glamsbjerg, Denmark<br />

Tel: +45 64 72 2055 • Fax: +45 64 72 2255<br />

E-mail: sales.dep@gw<strong>sprinkler</strong>.com<br />

Certificate No: 084h<br />

Product Name<br />

Nominal Type Temperature Ratings ( o C) LPCB Ref. No.<br />

Orifice<br />

Size<br />

(mm)<br />

GW-S-EL(1),(2),(3) 10 SP 57, 68, 79 (5mm bulb) 084h/01<br />

10 SU 57, 68, 79 (5mm bulb)<br />

GW-S-EL(1),(2),(3),(4) 10 SP 57, 68, 79 (5mm bulb)<br />

10 SU 57, 68, 79 (5mm bulb)<br />

GW-S-EL(1),(2),(3) 15 CU/P 57, 68, 79 (5mm bulb)<br />

15 SP 57, 68, 79 (5mm bulb)<br />

15 SU 57, 68, 79 (5mm bulb)<br />

GW-S-QR-EL(1),(2),(3) 10 SP 57, 68, 79 (quick response) 084h/02<br />

10 SU 57, 68, 79 (quick response)<br />

GW-S-QR-EL(1),(2),(3),(4) 10 SP 57, 68, 79 (quick response)<br />

10 SU 57, 68, 79 (quick response)<br />

GW-S-QR EL(1),(2),(3) 15 SP 57, 68, 79 (quick response)<br />

15 SU 57, 68, 79 (quick response)<br />

15 CU/P 57, 68, 79 (quick response)<br />

Notes:<br />

1) Also approved with chrome <strong>and</strong> painted finishes.<br />

2) To be installed, operated <strong>and</strong> maintained in accordance with the GW Sprinkler A/S Installation, Operating <strong>and</strong> Maintenance Manual.<br />

3) Sprinklers marked EL incorporate a ‘Metron’ actuator.<br />

4) This <strong>sprinkler</strong> is fitted with a pintle to denote that it has a 15mm nominal thread size.<br />