PROTECTIVE FUNCTION DETAIL<br />

The Relay Protective Trip Functions are detailed in Table 1 (shown again here for convenience).<br />

Table 1 Relay Protective Trip Functions<br />

ANSI Type No Menu Description Description<br />

Unused<br />

The relay is disabled<br />

59 Over Volts Over Voltage Relay<br />

27 Under Volts Under Voltage Relay<br />

81O Over Freq Over Frequency Relay<br />

81U Under Freq Under Frequency Relay<br />

50 Over Amps Instantaneous Over Current Relay<br />

37 Under Amps Instantaneous Under Current Relay<br />

50N Over Amps Instantaneous Over Neutral Current Relay<br />

32R Reverse Pwr Reverse Power Relay<br />

32O Over Power Forward Power Relay<br />

40Q Reverse VAr Reverse VAr Relay<br />

47 UnBal Volts Unbalanced Voltage Relay<br />

46 UnBal Amps Unbalanced Current Relay<br />

51V I/T+V.R. Time Over Current with Voltage Restraint Relay<br />

51 I/T Time Over Current Relay<br />

51G Gnd Fault Neutral Ground Fault Relay<br />

25 Sync Synchronism Check Relay<br />

25D Sync+DB Synchronism Check with Dead Bus Relay<br />

47 Phase Order Phase Sequence Relay<br />

Logical AND<br />

Logical OR<br />

Logical NAND<br />

Logical NOR<br />

Logical XOR<br />

Logical Vote<br />

Logical Disc<br />

Alarm<br />

Unack Alarm<br />

Will trip if all 3 inputs are tripped<br />

Will trip if any input is tripped<br />

Will trip unless all 3 inputs are tripped<br />

Will trip if any input is not tripped<br />

Will trip if the 3 inputs are not in the same state<br />

Will trip if at least 2 inputs are tripped<br />

Will trip if there is a discrepancy between inputs<br />

Will trip if an alarm situation exists<br />

Will trip if an alarm has not been acknowledged<br />

Accuracy levels <strong>and</strong> resolution of trip settings are detailed in ACCURACY AND RESOLUTION<br />

(located in the product specification section) unless otherwise stated.<br />