13.01.2015 Views

Installation and Operating Instructions - Crompton Instruments

Installation and Operating Instructions - Crompton Instruments

Installation and Operating Instructions - Crompton Instruments

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

There is a relationship between the phase angle <strong>and</strong> the slip frequency settings. When one<br />

parameter is adjusted, the setting range of the other may be automatically adjusted to prevent a<br />

condition where the relay may never close.<br />

CAUTION: This trip relay can be configured to Latch. This feature may be<br />

undesirable, if enabled in error.<br />

TYPE 25D — SYNCHRONISING/SYNCHRONISM-CHECK WITH DEAD BUS<br />

This function operates as a permissive relay, where the ‘not tripped’ condition indicates that the<br />

two systems are within the permitted limits to allow synchronism. A ‘tripped’ condition indicates<br />

that the systems are not within the allowable limits, <strong>and</strong> synchronism is not possible.<br />

The status display will indicate 25D# (relay is tripped) when the relay is not in synchronism. The<br />

display indication will disappear when synchronism is achieved, or when the BUS voltage is<br />

below the ‘Deadbus’ setting.<br />

When failsafe is set to ‘yes’, the relay contacts will energize when the GEN <strong>and</strong> BUS circuits are<br />

in synchronism. An out-of-sync condition, or loss of auxiliary supply, will de-energize the relay<br />

contacts.<br />

Brief details<br />

The relay either:<br />

(a) operates when the “Bus” <strong>and</strong> “Generator” signals are within the selected limits of<br />

frequency, phase angle, voltage <strong>and</strong> the phase sequence of the “Generator” voltage<br />

inputs is correct for the duration of the selected delay<br />

or:<br />

(b) the voltage on the “Bus” voltage input is below the selected limit <strong>and</strong> the phase<br />

sequence of the “Generator” voltage inputs is correct for the duration of the selected<br />

delay to permit or to cause the paralleling of two circuits. The relay will return to the<br />

“tripped” condition when any one of the conditions detailed above become invalid. The<br />

time delay is used on the transition to the “not tripped” condition.<br />

Parameters<br />

You must specify the following parameters for operation of the synchronising relay:<br />

●<br />

The maximum permitted phase angle between the “Bus” input voltage <strong>and</strong> the<br />

reference “Generator” voltage (V1, VA, or V1-2),<br />

●<br />

The maximum permitted voltage difference between the “Bus” input voltage <strong>and</strong> the<br />

reference “generator” voltage,<br />

●<br />

The maximum permitted frequency difference between the “Bus” <strong>and</strong> “Generator”<br />

(slip frequency)<br />

●<br />

The maximum voltage that may be present on the “Bus” voltage input before the phase,<br />

frequency <strong>and</strong> voltage difference conditions are required to qualify the trip condition (for<br />

levels below this voltage the relay will operate providing that the phase sequence of the<br />

“Generator” voltage inputs is correct).<br />

●<br />

The time for which these conditions must be true<br />

• The minimum voltage level, below which they function.<br />

53

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!