Parameter details<br />
Range of Frequency Trip point (Trip Point)<br />
Range of Diff (Diff)<br />
Range of Time Delay (Time Delay)<br />
40 — 70 Hz<br />
0.1 — 10 Hz<br />
0 to 30 seconds<br />
LOGICAL TRIP FUNCTIONS<br />
Parameters<br />
You must specify the following parameters for operation of the logical trip functions:<br />
●<br />
The logical function type<br />
●<br />
The trips (relay numbers) to be included in the logic function (up to three)<br />
●<br />
The time delay from the logical condition becoming true to the relay adopting the<br />
“tripped” condition<br />
●<br />
The time delay from the logical condition becoming false to the relay returning to the<br />
“not tripped” condition<br />
Parameter details<br />
Logic Functions Supported AND Output true when all inputs true<br />
OR Output true when any input true<br />
NAND Output true except when all inputs true<br />
NOR Output true when no inputs are true<br />
XOR Output true when odd number of inputs are<br />
true<br />
Vote Output true when the majority of inputs are<br />
true<br />
Disc<br />
Output true when inputs are different<br />
Range of Delay to On Time<br />
0 — 30 Seconds<br />
Range of Delay to Off Time<br />
0 — 30 Seconds<br />