Parameter details<br />

Range of Frequency Trip point (Trip Point)<br />

Range of Diff (Diff)<br />

Range of Time Delay (Time Delay)<br />

40 — 70 Hz<br />

0.1 — 10 Hz<br />

0 to 30 seconds<br />

LOGICAL TRIP FUNCTIONS<br />

Parameters<br />

You must specify the following parameters for operation of the logical trip functions:<br />

●<br />

The logical function type<br />

●<br />

The trips (relay numbers) to be included in the logic function (up to three)<br />

●<br />

The time delay from the logical condition becoming true to the relay adopting the<br />

“tripped” condition<br />

●<br />

The time delay from the logical condition becoming false to the relay returning to the<br />

“not tripped” condition<br />

Parameter details<br />

Logic Functions Supported AND Output true when all inputs true<br />

OR Output true when any input true<br />

NAND Output true except when all inputs true<br />

NOR Output true when no inputs are true<br />

XOR Output true when odd number of inputs are<br />

true<br />

Vote Output true when the majority of inputs are<br />

true<br />

Disc<br />

Output true when inputs are different<br />

Range of Delay to On Time<br />

0 — 30 Seconds<br />

Range of Delay to Off Time<br />

0 — 30 Seconds<br />